Central Remote Controller
Installation Manual
16
-EN
3
Register the indoor units to the unit
Press the [
] and [
] buttons simultaneously for 4 seconds or more on the
All screen to move to "How to Display the "Servicing Menu" Screen (P.17-2)".
Perform "Obtain Address (
If you will not change the Central control address
(P.18-1-2))" of "Address Settings".
After performing "
If you will not change the Central control address (P.18-
2)", check that there is no error in the displayed number of connected units,
line address-indoor address, and Central control address (*1), then perform
"
If you will not change the Central control address (P.18-3)".
*1 If there is an error
• Check the power supply and wiring.
• To change the address, use the local remote controller or the unit ("
change the Central control address (P.19-3 to 4)").
• Repeat the setting in this section (3.Register the indoor units to the unit)
from the beginning.
4
Assign indoor units to zones 1 to 10
Perform "Change the Zone to which the Indoor Unit Belongs (Zone Settings)
(P.21-1 to 4)".
Return to the All screen and check if the displayed number of units matches
the number registered in the zone (*2).
*2 Indoor units that are not registered in a zone are not included in the number
of units on the All screen.
5
Operation confirmation
Check whether the indoor units can be operated from the Central Remote
Controller.
Also, check whether the operation of the local remote controller is reflected on
the Central Remote Controller.
6
Preparation for delivery
If an inspection code occurs during operation check, perform "Delete check history (P.26)".
This completes the test run for the controller.
For other detailed settings, refer to "Owner's Manual" and "Installation Manual (P17 to P34)".
Line address
Indoor address
Central control
address
Example of Obtain Address screen
Central control address
Example of zone setting (Central
control address) screen
Number of units that have been set
Zone No.
Summary of Contents for TCB-SC640U-E
Page 35: ...DEB5219151 2 ...