- 10 -
Cooling capacity
kW
10.0
12.5
Phase
3
3
Power source
V
380 – 415
380 – 415
Hz
50
50
COOLING
COOLING
Power consumption
kW
3.9
5.0
Power Factor
%
87
86
Running current
A
6.5
8.4
Starting current
A
42
50
Operating
Indoor unit
(High/Med./Low)
dB(A)
50/45/42
52/47/44
noise (SPL)
Outdoor unit
dB(A)
55
59
Name of refrigerant
R-22
R-22
Regrigerant
Charge volume
kg
3.1
3.2
Add. volume (20-50m)
g/m
60
60
Refrigerant control
Capillary tube
Capillary tube
Large side size *2
mm
ø 19 (ø 22)
ø 19 (ø 22)
Coupler style
Flare
Flare
Smaller side size
mm
ø 9.5
ø 9.5
Inter-
Coupler style
Flare
Flare
connection
Standard length
m
7.5
7.5
pipe
Maximum height length
m
50
50
(of one way) * 1
Max. height difference
m
20
20
if indoor unit higher
Outdoor unit higher
m
50
50
Condensate drain pipe diameter
mm
ø 32 (OD)
ø 32 (OD)
INDOOR UNIT
RAV-362U-PE
RAV-462U-PE
Model
Appearance colour
Black (Zinc galvanized steel + Thermal insulation)
Height
mm
350
350
Dimensions
Width
mm
1130
1130
Depth
mm
740
740
Net weight
kg
53
53
Heat exchanger type
Finned tube
Finned tube
Indoor fan type
Centrifugal Fan
Centrifugal Fan
Air flow volume
m
3
/h
1680
1860
Fan motor output
W
80
90
CEILING PANEL Model
RBC-U462PG(W)-PE
RBC-U462PG(W)-PE
Appearance colour
Silky mist (Munsell 1Y8.9/0.5)
Silky mist (Munsell 1Y8.9/0.5)
Height
mm
28
28
Dimensions
Width
mm
1290
1290
Depth
mm
840
840
Net Weight
kg
10
10
Air filter
Washable
Washable
OUTDOOR UNIT
RAV-362A8-PE
RAV-462A8-PE
Model
Appearance colour
Bronze white (Munsell 6Y7.5/1)
Bronze white (Munsell 6Y7.5/1)
Height
mm
1240
1240
Dimensions
Width
mm
930
930
Depth
mm
385
385
Net Weight
kg
104
112
Heat exchange type
Finned tube
Finned tube
Outdoor fan type
Propeller fan
Propeller fan
Air flow volume
m
3
/h
6000
6000
Fan motor output
39 + 63
105 + 105
Compressor
Model
YH406JA
YH506JA
Output
kW
3.0
3.75
High pressure switch, Fuse,
High pressure switch, Fuse,
Protective device
Overload relay, Crankcase heater,
Overload relay, Crankcase heater,
Inner overload relay
Inner overload relay
RAV-462U-PE
RAV-362U-PE
ITEM
MODEL
Note 1: These mean actual length.
Note 2: (ø22) should be used when the length of pipe exceeds 30m.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807