- 53 -
182A-PE
242A-PE/242AB-PE
362A8-PE
462A8-PE
10.3 Piping length/additional refrigerant volume
20
Model (RAV-)
Piping length less than (m)
Less
than
45mm
1.25
1.25
Less
than
5mm
1.2
1.5
2.7
2.8
Less
than
15mm
1.35
1.6
2.95
3.05
Recharge amount of interchange time (kg)
Less
than
30mm
1.8
2.1
3.6
3.7
Less
than
50mm
4.6
4.7
Less
than
25mm
1.6
1.85
3.25
3.35
Additional amount of refrigerant
at installation site (kg)
Less
than
35mm
0.75
0.75
Less
than
30mm
0.35
0.45
0.5
0.5
Less
than
25mm
0.15
0.2
0.25
0.25
Less
than
40mm
1.0
1.0
Less
than
50mm
1.5
1.5
Less
than
10mm
1.3
1.55
2.85
2.95
Less
than
20mm
1.45
1.65
3.1
3.2
Less
than
35mm
3.85
3.95
Less
than
40mm
4.1
4.2
Less
than
45mm
4.35
4.45
•
The amount of refrigerant put into the outdoor unit at the factory is equivalent to the one that fills up 20m length of
refrigerant pipe.
•
If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of
the pipe exceeds 20m, add the refrigerant R-22.
•
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed
amount of the replenishment of the refrigerant is shown in the table above.
The permissible amount of refrigerant is the prescribed 50g.
•
For RAV-362A8-PE and RAV-462A8-PE, if the length of pipe exceeds 30m the diameter of the gas pipe must be increased
by one rank (i.e. 19.0
→
22.2).
Filled at
factory