– 90 –
Function selection item No. (FC) list
3. Monitor function
The sensor temperature or operational status of indoor unit, outdoor unit, or remote controller can be monitored.
FC
Item
Contents
At shipment from factory
01
Filter sign lighting time
0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
0005: Clogging sensor used
0000: None
02
Filter stain level
0000: Standard
0001: Heavy stain (Half of standard time)
0000: Standard
06
Heating suction temp. shift
0000: No shift
0002: +2°C
to
0001: +1°C
0010: +10°C
0002: +2°C
10
Type
0000: IMS duct
0000: IMS duct
11
Indoor unit capacity
0000: Undecided
0001 to 0034
According to capacity type
M07: 0001
M10: 0003
M13: 0005
M16: 0007
17
Cooling suction temp. shift
0000: No shift
0002: +2°C
to
0001: +1°C
0010: +10°C
0000: No shift
1E
In automatic cooling/heating,
temp. width of cool
→
heat,
heat
→
cool mode selection
control point
0000: 0 deg
to
0010: 10 deg
0003: 3 deg
(Ts±1.5)
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
28
Automatic reset of power
failure
0000: None
0001: Provided
0000: None
32
Sensor selection
0000: Body TA
sensor
0001: Remote controller
sensor
0000: Body sensor
5d
External static pressure
0000: Depends on
DIPSW 501-1,-2
1
Push the [
∧
] / [
∨
] button to select “4. Monitor
function” on the “Field setting menu” screen, then push
the “
Set” [
F2] button.
Æ
Push the [
∧
] / [
∨
] button to select the code to check
data.
2
Push the [
CANCEL] button to return to the “Field
setting menu” screen.
SET DATA
External static pressure
0000
Depends on
DIPSW 501-1,-2
0001
10 Pa
0002
20 Pa
0003
35 Pa
0004
45 Pa
Monitor function
Code
00
Data
0024
Return
Set
Item code
Data name
Unit
01
Room temperature
(Remote controller)
°C
02
Indoor suction temperature (TA)
°C
03
Indoor heat exchanger (Coil)
temperature (TCJ)
°C
04
Indoor heat exchanger (Coil)
temperature (TC)
°C
∗
07
Indoor fan revolution frequency
rpm
∗
F2
Indoor fan calculated operation
time
×100h
F3
Filter sign time
×1h
∗
F8
Indoor discharge temperature*1
°C
Indo
or uni
t dat
a
Item code
Data name
Unit
60
Outdoor heat exchanger (Coil)
temperature (TE)
°C
61
Outside temperature (TO)
°C
62
Compressor discharge
temperature (TD)
°C
63
Compressor suction temperature
(TS)
°C
6A
Operation current (× 1/10)
A
70
Compressor operation frequency
rps
72
Outdoor fan revolution frequency
(Lower)
rpm
F1
Compressor calculated operation
time
×100h
O
u
tdoo
r unit dat
a