11-5. Judgment of Trouble by Every Symptom
11-5-1. Indoor Unit (Including Remote Controller)
(1) Power is not turned on (Does not operate entirely)
<Primary check>
1. Is the supply voltage normal?
2. Is the normal voltage provided to the outdoor unit?
3. Is the crossover cable connected properly?
4. Is the fuse (F01) blown?
• Be sure to disconnect the motor connector CN210 after shut off the power supply, or it will be a cause of
damage of the motor.
Turn off power
supply once, and 5
second later, turn it
on again.
Is OPERATION
lamp blinking?
Is it possible to
turn on power
supply by
pressing [
]
button on remote
control?
NO
NO
NO
YES
YES
YES
Does
transmission
mark on
remote control
flash normally,
and is its signal
transmitted
properly?
YES
Does
transmission
mark on
remote control
flash normally,
and is its signal
transmitted
properly?
Remote control is
defective.
Operation
Check item
Conceivable
principle cause
Measure
Item by symptoms
Refer to (4)
"Troubleshooting for
Remote Control."
Unit operates
normally.
Is fuse (F01) of
indoor control
board blown?
Is the
voltage
across C08
measured
DC 310V~340V?
NO
NO
Parts (R01, R03,
R04, DB01, C01,
C08, IC01, and
T01) are
defective.
Are DC 5V,
DC 12V
supplied to
main P.C.
board?
YES
NO
YES
Parts of power
supply circuit are
defective
Does fan
motor
connector
between
1
and
4
short-
circuit?
YES
NO
Replace main P.C.
board.
Microcomputer
is defective.
Parts are
defective
Replace motor
Summary of Contents for ras-m07g3dv-e