background image

7

Installation Manual

Outdoor Unit

5

  Installation of outdoor unit

 

Installation Location

•  A place which can bear the weight of the outdoor unit and does not cause 

an increase in noise level and vibration.

•  A place where the operation noise and air discharge do not disturb 

neighbours.

•  A place which is not exposed to strong wind.
•  A place free of combustible gas.
•  A place which does not block a passageway.
•  A place where the drain water does not cause any problems.
•  A place where there are no obstructions near its air intake or air discharge.

Installation in the following places may result in trouble:
•  A place with a lot of machine oil.
•  A place with saline-rich atmosphere such as a coastal area.
•  A place with high level of sul

fi

 de gas.

•  A place where high-frequency waves are likely to be generated, such as 

from audio equipment, welders, or medical equipment.

Do not install the unit in such places.

 

Precautions for Installation

•  When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet.

•  If the outdoor unit is to be mounted on a wall, make sure the base plate 

supporting it is sturdy enough.

•  The base plate should be designed and manufactured to maintain its 

strength over a long period of time, and suf

fi

 cient consideration should be 

given to ensure that the outdoor unit will not fall.

•  When the outdoor unit is installed in a place that is always exposed to 

strong wind such as a coastal area or on a high story of a building, secure 
the normal fan operation using a duct or a wind shield.

•  Especially in windy areas, install the unit in such a way as to prevent the 

admission of wind.

•  When the outdoor unit is to be mounted high on a wall, take particular care 

to ensure that parts do not fall, and that the installer is protected.

•  When doing installation work at ground level, it is usual to make wiring and 

pipe connections to the indoor units 

fi

 rst, and then to make connections to 

the outdoor units.
However, if outdoor work is dif

fi

 cult, you can change the procedure.

For example, by making adjustments to the wiring and piping lengths on 
the inside (rather than the outside).

•  When using an air conditioner under low outside temperature conditions 

(Outside temp: -5 °C or lower) In COOL mode, prepare a duct or wind 
shield so that it is not affected by the wind.

Necessary Space for Installation

If you need to install the outdoor unit in a location where there are some 
obstructions or a wall, secure sufficient space as shown in the figure below.
The cooling/heating effect may be reduced by 10%.

 
 

 

100 mm or more

100 mm or more

600 mm or more

600 mm or more

600 mm or more

Draining Off the Water from the Outdoor Unit

Install 2 waterproof rubber caps and the drain nipple to drain off the 
water from the outdoor unit.

•  Seal the knock-out holes and screw/thread areas tightly using a silicon 

adhesive or a caulking compound.

•  Use a drain pan to apply a centralized drain.

Drain nipple

Water-proofing rubber cap

Installation in Regions with Snowfall and Cold Temperatures

Do not use waterproof rubber caps or a drain nipple.

•  If you need to install the outdoor unit in a location where there is a 

possibility of the drain freezing, pay close attention so that the drain does 
not become frozen.

•  To protect the outdoor unit from snow, install the outdoor unit on a holding 

frame, and attach a snow protection hood and plate.

•  Keep the outdoor unit at least 500 mm above the snow accumulation line.

Snow protection plate

Snow protection hood

At least 500 mm

Snow accumulation line

Holding frame

Anchor bolts

Front

Fixing the Outdoor Unit

Fix the outdoor unit using attachment bolts.

•  Use 8 mm or 10 mm anchor bolts and nuts.
•  Do not allow the attachment bolts to protrude by more than 15 mm.
•  Install the outdoor unit at ground level.
•  Attach the vibration-proof rubber pads under the 

fi

 xing legs.

GOOD

BAD

Drain nipple mounting hole

Drain hole

15 mm or 

less

Mounting leg

Absorb vibration 

with vibration-proof 

rubber pads

Foundation

Foundation

If only the end 

of the 

mounting leg 

is supported, 

it may 

deform.

Do not support 

the outdoor unit 

only with the 

mounting leg.

Foundation

Bottom plate of 

outdoor unit

Support the bottom surface of the 

mounting leg that is in contact with 

and underneath the bottom plate of 

the outdoor unit.

600

351

54

330

100

99

508

1116691099_(01) EN.indd   7

1116691099_(01) EN.indd   7

9/22/15   5:59 PM

9/22/15   5:59 PM

Summary of Contents for RAS-2M14S3AV-E

Page 1: ... Manual Outdoor Unit Model name RAS 3M18S3AV E RAS 2M18S3AV E RAS 2M14S3AV E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M18S3AV E and RAS 2M14S3AV E English Installation Manual Outdoor Unit ...

Page 2: ...ng 10 9 Test run 10 10 Pump down Operation 12 11 Troubleshooting 12 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to the install...

Page 3: ...ity of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves after effects and requires hospitalization or extended out pa...

Page 4: ...oles must be incorporated in the fixed wiring Turn off main power supply before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cables correctly If the connecting cables are connected wrongly electric parts may be damaged Check the earth wire that it is not broken or disconnected before installation Do not install...

Page 5: ...s or the specified parts Failure to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly ear...

Page 6: ... disturb neighbours This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed Failure to do so may cause electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage...

Page 7: ... combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class RAS...

Page 8: ... to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoor unit in a location where there are some obstructions or a wall secure sufficient ...

Page 9: ...hexagon wrench 1 Connect a charge hose Make sure that the Handle Hi of the gauge manifold valve is closed fully Connect the port of the gauge manifold valve and the service port Valve core Setting Pin using the charge hose NOTE If a control valve or charge valve is attached to the charge hose leak of R410A refrigerant can be avoided 2 Open the Handle Low of the gauge manifold valve fully then oper...

Page 10: ...r refrigerant leaks may be required depending on European or local legislation Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Heat proof bubble polyethylene Gas Leak Inspection Perform a gas leak inspection for the flare nut connections valve stem connection and service port cap without fail Use a leak detector exclusively manufactured for R410A Fl...

Page 11: ...it Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 2 3 5 5 30 55 L N Earth wire Earth wire Powe...

Page 12: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 9 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room th...

Page 13: ...lve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start over the operati...

Page 14: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691099 ...

Reviews: