background image

3

Installation Manual

Outdoor Unit

 

CAUTION

New refrigerant air conditioner installation 

THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT (R410A), WHICH DOES 
NOT DESTROY THE OZONE LAYER. 
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membranes, 
and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. 
As well as the adoption of this new refrigerant, refrigerating machine oil has also been 
changed. Therefore, during installation work, be sure that water, dust, former refrigerant, 
or refrigerating machine oil does not enter the refrigeration cycle of a new-refrigerant air 
conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging 
port connecting sections on the main unit are different from those for the conventional 
refrigerant, and different size tools are also required. For connecting pipes, use new and 
clean piping materials with high pressure withstand capabilities, designed for R410A only, 
and ensure that water or dust does not enter. Moreover, do not use any existing piping as its 
pressure withstand may be insufficient and may contain impurities. 

 

DANGER

•  The manufacturer shall not assume any liability for the damage caused by not observing 

the description of this manual. 

•  For use by qualified persons only. 
•  Means for disconnection from the supply having a contact separation of at least 3 mm in 

all poles must be incorporated in the fixed wiring. 

•  Turn off main power supply before attempting any electrical work. Make sure all power 

switches are off. Failure to do so may cause electric shock. 

•  Connect the connecting cables correctly. If the connecting cables are connected wrongly, 

electric parts may be damaged. 

•  Check the earth wire that it is not broken or disconnected before installation. 
•  Do not install near concentrations of combustible gas or gas vapors. Failure to follow this 

instruction can result in fire or explosion. 

•  To prevent overheating the indoor unit and causing a fire hazard, place the unit well away 

(more than 2 m) from heat sources such as radiators, heaters, furnace, stoves, etc. 

•  When moving the air conditioner for installing it in another place again, be very careful 

not to get the specified refrigerant (R410A) with any other gaseous body into the 
refrigeration cycle. If air or any other gas is mixed in the refrigerant, the gas pressure in 
the refrigeration cycle becomes abnormally high and it resultantly causes burst of the pipe 
and injuries on persons. 

•  In the event that the refrigerant gas leaks out of the pipe during the installation work, 

immediately let fresh air into the room. If the refrigerant gas is heated by fire or something 
else, It causes generation of poisonous gas. 

•  When installing or re-installing the air conditioner, do not inject air or other substances 

besides the designated refrigerant “R410A” into the refrigerating cycle.
If air or other substances are mixed, an abnormal pressure can occur in the refrigerating 
cycle, and this can cause an injury due to a pipe rupture. 

1116691099_(01) EN.indd   3

1116691099_(01) EN.indd   3

9/22/15   5:59 PM

9/22/15   5:59 PM

Summary of Contents for RAS-2M14S3AV-E

Page 1: ... Manual Outdoor Unit Model name RAS 3M18S3AV E RAS 2M18S3AV E RAS 2M14S3AV E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M18S3AV E and RAS 2M14S3AV E English Installation Manual Outdoor Unit ...

Page 2: ...ng 10 9 Test run 10 10 Pump down Operation 12 11 Troubleshooting 12 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to the install...

Page 3: ...ity of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves after effects and requires hospitalization or extended out pa...

Page 4: ...oles must be incorporated in the fixed wiring Turn off main power supply before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cables correctly If the connecting cables are connected wrongly electric parts may be damaged Check the earth wire that it is not broken or disconnected before installation Do not install...

Page 5: ...s or the specified parts Failure to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly ear...

Page 6: ... disturb neighbours This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed Failure to do so may cause electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage...

Page 7: ... combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class RAS...

Page 8: ... to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoor unit in a location where there are some obstructions or a wall secure sufficient ...

Page 9: ...hexagon wrench 1 Connect a charge hose Make sure that the Handle Hi of the gauge manifold valve is closed fully Connect the port of the gauge manifold valve and the service port Valve core Setting Pin using the charge hose NOTE If a control valve or charge valve is attached to the charge hose leak of R410A refrigerant can be avoided 2 Open the Handle Low of the gauge manifold valve fully then oper...

Page 10: ...r refrigerant leaks may be required depending on European or local legislation Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Heat proof bubble polyethylene Gas Leak Inspection Perform a gas leak inspection for the flare nut connections valve stem connection and service port cap without fail Use a leak detector exclusively manufactured for R410A Fl...

Page 11: ...it Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 2 3 5 5 30 55 L N Earth wire Earth wire Powe...

Page 12: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 9 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room th...

Page 13: ...lve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start over the operati...

Page 14: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691099 ...

Reviews: