Item
3. Outdoor fan
motor control
Operation flow and applicable data, etc.
The blowing air volume at the outdoor unit side is controlled.
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
Tap
RAS-
25PAVPG
-ND
RAS-35
PAVPG-ND
Tap
RAS-25
PAVPG-ND
RAS-35
PAVPG-ND
W0
0
0
W9
600
700
W1
600
600
WA
600
700
W2
600
600
WB
600
700
W3
600
600
WC
600
700
W4
600
600
WD
600
700
W5
600
600
WE
700
700
W6
600
600
WF
850
850
W7
600
600
W8
600
650
Air conditioner ON
(Remote controller)
YES
YES
NO
NO
Indoor unit controller
Fan motor ON
3) Fan lock
4) Motor operates as shown in the table below.
1) Outdoor unit
operation command
(Outdoor fan control)
Air conditioner
OFF
Alarm
display
2) Fan speed
≥
400.
(by strong wind)
when the motor OFF.
Fan motor OFF continues
(Use wind for heat
exchanging)
In Cooling operation
In Heating operation
MIN
MAX
MIN
MAX
MIN
MAX
To≥10°C
W7
W8
W9
To ≥ 38°C
W6
WB
W8
WE
WA
WE
To ≥ 5°C
W9
WB
WE
To ≥ 29°C
W5
WA
W7
WE
W9
WE
To ≥ -3°C
WE
WE
WE
To ≥ 15°C
W3
W7
W5
W9
W7
WB
To ≥ -10°C
WE
WE
WE
To ≥ 5°C
W2
W5
W4
W7
W6
W9
To < -10°C
WE
WE
WE
To ≥ 0°C
W1
W3
W3
W5
W4
W7
When To is abnormal
WE
WE
WE
To ≥ -4°C
W1
W2
W2
W4
W3
W5
To < -4°C
OFF
OFF
OFF
W3
W1
W4
When To is abnormal
OFF
WB
OFF
WE
W1
WE
TO
To
Outdoor fan speed (rpm)
RAS-25PAVPG-ND
RAS-35PAVPG-ND
Fan operation
Hz < 16.8
16.8 < Hz < 37.2
37.2 < Hz
Hz < 13.2
13.2 < Hz < 27.0
27.0 < Hz
RAS-25PAVPG-ND
RAS-35PAVPG-ND
Fan operation
MIN
MAX
MIN
MAX
MIN
MAX
Hz < 21.0
21.0 < Hz < 42.0
42.0 < Hz
Hz < 19.2
19.2 < Hz < 36.6
36.6 < Hz
Comp. Hz
Comp. Hz
FILE NO. SVM-17050