NOTE :
• The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
Max. : 25m
Deoxidized copper pipe
Outer dia. : 9.52mm (35)
: 12.7mm (45)
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allo
w
ab
le height
diff
erence :
10m
Allo
w
ab
le pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Pulse Modulating
valve at liquid side
Ø1.
0
x 80
Ø1.
0
x 80
TD
4-way valve
Compressor
KTN150D42UFZ
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Propeller fan
Refrigerant amount : 1.05kg
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
Min. : 2m
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Thickness : 0.8mm
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
Tcj
RAS-35PKVPG-ND / RAS-35PAVPG-ND
Strainer
Dryer
FILE NO. SVM-17050
- 21 -