8-18.Outdoor Quiet Control
8-18-1. Purpose
For the users who concern about noise of the outdoor
unit, this control controls the maximum revolutions of
the compressor to reduce the noise.
8-18-2. Description
To reduce noise, [RESET] button of the indoor unit is
kept pushed for 20 seconds.
The number of revolution for the indoor fan motor and
the setup temp value are kept as they are.
With Quiet control/Non-select method
8-18-3. Operation
As shown in the table, the maximum revolution number
of compressor can be reduced.
As the maximum number of revolution of the
compressor is restricted, the rise-up performance at
the start time is weakened.
Maximum number of revolution of compressor
at normal time and Quiet control time
8-19. 8°C HEAT Operation
(-ND Model Only)
8-19-1. Start 8°C HEAT
Operation When the Air
Conditioner is Stopped
1) Pushing [8°C] button turns on the Operation
lamp (Green) of the main unit is turned on and
the HEAT operation of set temperature 8°C
starts.
8-19-2. Start 8°C HEAT
Operation When the Air
Conditioner is Operating
1) Pushing [8°C] button shifts the operation to
HEAT operation with set temperature 8°C.
NOTE
• In case of COOL (including automatic cooling) or
DRY operation, 8°C HEAT operation starts approx.
3 minutes after operation stop.
In case of HEAT operation, the operation shifts to
8°C HEAT operation as it is.
• If the timer operation has been set up before 8°C
HEAT operation, the setup is released when 8°C
HEAT operation starts.
• When [8°C] button is pushed again during 8°C
HEAT operation, the status returns to that before
8°C HEAT operation.
• When the operation shifts from 8°C HEAT operation
to the normal HEAT operation, the cold draft
preventive control works.
Therefore the hot air may blow out after approx. 5
minutes.
8-19-3. Stop
1) Pushing
button stops the operation.
The air conditioner is controlled according to the room
temperature 8°C as a standard.
The room temperature may be a little off the room
temperature 8°C due to the room size or installation
condition of the unit.
RAS-07PKVP-E
RAS-07PKVP-ND
RAS-10PKVP-E
RAS-10PKVP-ND
RAS-13PKVP-E
RAS-13PKVP-ND
Normal
time
(rps)
Quite
controlled
(rps)
Normal
time
(rps)
Quite
controlled
(rps)
Normal
time
(rps)
Quite
controlled
(rps)
Cooling
46
40
57
49
75
59
Heating
80
70
93
72
92
72
RAS-16PKVP-E
RAS-16PKVP-ND
RAS-18PKVP-E
RAS-18PKVP-ND
Normal
time
(rps)
Quite
controlled
(rps)
Normal
time
(rps)
Quite
controlled
(rps)
Cooling
88
69
100
80
Heating
98
77
100
80
Select “Control” or “No control” by keeping
[RESET] button pushed for 20 seconds.
(“No control” as the factory default)
↓
• Exchanging from “No control” to “Control”:
Beep sound is heard and the operation
LED 5Hz flashes for 5 seconds.
• Exchanging from “Control” to “No control”:
Beep sound is heard.
(Operation LED does not flash.)