BACKUP OPERATION
(EMERGENCY OPERATION)
This product offers backup modes of operation to get over certain emergency situations. If a fault occurs in one of
the compressors, it is possible to operate the system on an emergency basis by operating only the remaining
compressor(s), (compressor backup operation).
If one of the outdoor units fails in a combined outdoor unit system, the system can be operated on an emergency
basis by keeping only the remaining outdoor unit(s), (outdoor unit backup operation).
Perform backup operation setting in accordance with the procedure described below.
Note for Backup Operation
The method of backup operation differs according to the contents of fault as shown in the table below.
Contents of fault
One of the compressors in the same unit fails (see Note 1)
All the compressors in the same unit fail
A fault occurs in a compressor motor coil (e.g. a layer short-circuit)
A fault occurs in a refrigerating cycle part, fan or related part, or electrical part
A fault occurs in a temperature sensor or pressure sensor
Method of backup operation
Compressor backup (see Note 2)
Outdoor unit backup or
coolingseason outdoor unit
backup (see Notes 1, 3, 4 and 5)
Setting procedure
Go to page 37.
Go to page 38 or 39.
Note 1:
If the compressor has failed due to a fault in its motor coil (e.g. a layer short-circuit), do not preform
compressor backup operation because of severe oil degradation. It could damage other outdoor units.
Note 2:
Keep the number of backed-up outdoor units under compressor backup operation to one in the system
(single refrigerant line).
For a three-compressor model, the backing up of two faulty compressors is prohibited.
Note 3:
Keep the number of backed-up outdoor units under outdoor unit backup operation to one in the system
(single refrigerant line).
Note 4:
It is prohibited to combine compressor backup operation and outdoor unit backup operation.
Note 5:
With a two-outdoor unit system containing an
MMYMAP1604
∗
(or MAP1404
∗
) and an
MMY-MAP1204
∗
(or MMY-MAP0804
∗
or MAP1004
∗
), do not preform
outdoor unit backup operation to back up the
MMY-MAP1604
∗
(or MAP1404
∗
). It could lead to
compressor failure due to the abnormal operation.