Error Clearing Function
Clearing From the Main Remote Controller
l
Error clearing in outdoor unit
Error of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the
indoor units operated by the remote controller is connected. (Error of the indoor unit is not cleared.)
For clearing errors, the service monitor function of the remote controller is used.
<Method>
TEMP.
ON / OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
No.
R.C.
TIMER SET
MODE
FAN
SET DATA
SETTING
1 3
4
2
Section A
7-segment display
[A] [B]
[ E r ] [ ]
7-segment display
[A] [B]
[ E r ] [ C L ]
Set the rotary switches on the interface P.C. board of
the header unit as follows.
Set SW01/SW02/SW03 to [2/16/1]
Press the push-switch SW04 on the same board for
5 seconds or more.
[ C L] is displayed in 7-segment display [B] on the
board (for 5 seconds), and the error is completely
cleared.
Interface P.C. board
SW04
SW05
SW02
SW03
SW01
7-segment display [A]
7-segment display [B]
<Rotary switches>
1
Change the mode to service monitor mode by pushing
CL
+
TEST
buttons simultaneously for 4 seconds or more.
2
Using
TEMP.
buttons, set CODE No. to “
FF
”.
3
The display in Section A in the following figure is counted with
interval of 5 seconds as “
0005
”
→
→
→
→
→
“
0004
”
→
→
→
→
→
“
0003
”
→
→
→
→
→
“
0002
”
→
→
→
→
→
“
0001
”
→
→
→
→
→
“
0000
”
.
When the count arrives “
0000
”, the error is cleared.
∗
However, counting from “
0005
” is repeated on the
display.
4
When
TEST
button is pushed, the status returns to the normal
status.
l
Error clearing in indoor unit
Error in the indoor unit is cleared by
ON / OFF
button on the
remote controller. (Only error of the indoor unit connected
with operating remote controller is cleared.)
Clearing Error by Using Switches on the Interface P.C. Board of the Header Unit
Using the switches on the interface P.C. board of the header unit, this function is to clear the currently detected
error for each refrigerant circuit system without resetting the power supply.
Errors in both outdoor and indoor units are once cleared, and error detection is performed again.
Clearing Error by Resetting Power
This function is provided to clear error in a system by resetting the power of all the outdoor and the indoor units.
As same as the clearing method by the interface P.C. board, errors of both the outdoor and the indoor units are
once cleared, and error detection is performed again.
<Method>
(1) Be sure to reset power of both the outdoor and the indoor units.
(2) Turn on the power of the indoor unit prior to the power of the outdoor unit.
(If the power is turned on in reverse order, a check code [E19] (No. of header unit error) is output.)
NOTE
After power reset, it requires usually 3 minutes to power-on due to the initial communication of the system.
In some cases, it requires max. 10 minutes.