Indoor units to have their addresses initialized
Resetting the Address (Resetting to the Factory Default (Address Undecided))
Method 1
Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to “
0099
” using a wired remote controller.
(For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerant line at once from the outdoor unit.
1
Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.
1) Disconnect the relay connectors between the [
U1
,
U2
] and [
U3
,
U4
] terminals.
(Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of
SW30
on the interface P.C. board of the header outdoor unit if the switch is OFF.
(Leave it as it is if it has already been set to ON.)
3
Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and
SW03
to 1, 1, 1
respectively.
4
After a time “
U.1.L08
” appears on the 7-segment display if the address clearing has been completed
successfully. If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with
other refrigerant lines. Check the connection of the relay connectors between [
U1, U2
] and [
U3, U4
].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be
cleared.
5
Set the addresses again after finishing the clearance.
2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses.
About one minute after turning on the power, confirm that the 7-segment display on the header outdoor
unit indicates “
U.1. - - -
” and operate the interface P.C. board on the header outdoor unit of the refrigerant
line as follows.
SW01
2
2
SW02
1
2
SW03
2
2
SW04
Confirm that the 7-segment display indicates “A.d.buS”
and turn SW04 ON for more than 5 seconds.
Confirm that the 7-segment display indicates
“A.d.nEt” and turn SW04 ON for more than 5 seconds.
Clearable addresses
System/indoor unit/group address
Central control address
16