– 55 –
FILE NO. SVM-
16041
*1 The TF / TSA / TOA sensors are equipped only with some types of indoor units. The data does not appear
for other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
∗
, 5
∗
... U1 outdoor unit (Center unit)
2
∗
, 6
∗
... U2 outdoor unit (terminal unit 1)
3
∗
, 7
∗
... U3 outdoor unit (terminal unit 2)
4
∗
, 8
∗
... U4 outdoor unit (terminal unit 3)
*5 Only CODE No. 5
∗
of U1 outdoor unit (Center unit) is displayed.
Individual
data 2 of
outdoor unit
*4
CODE No.
Data
Format
Unit
Remote controller display example
U1 U2 U3 U4
57 67 77 87 Heat sink temperature of outdoor fan IPDU
59 — — — Pressure release *5
5F 6F 7F 8F Horse power of outdoor unit
HP
54 64 74 84
Heat sink temperature of compressor
IPDU1
55 65 75 85
Heat sink temperature of compressor
IPDU2
56 66 76 —
Heat sink temperature of compressor
IPDU3
58 — — —
In heat/cool collecting control *5
5A — — —
Discharge temperature release *5
0: Normal
1: In collecting control
0: Normal
1: In release control
5B — — —
Terminal unit release
(U2 / U3 / U4 outdoor unit) *5
[0642]=64.2 rps
[0058]=Mode 58
[0024]=24 ˚C
[0010] = In heat collecting control
[0001] = In cool collecting control
[0010] = In pressure release control
[0001] = In discharge temperature
release control
[0100] = In U2 outdoor unit release
control
[0010] = In U3 outdoor unit release
control
[0001] = In U4 outdoor unit release
control
[0016]=16HP
50
51
52
53
60
61
62
63
70
71
72
73
80
81
—
83
Rotation of compressor 1
Rotation of compressor 2
Rotation of compressor 3
Outdoor fan mode
rps
rps
rps
Mode
x10
x10
x10
x1
x1
x1
x1
x1
x1
˚C
˚C
˚C
˚C