– 42 –
FILE NO. SVM-
16041
DN
5d
60
Item
High ceiling selection
(Selection of air volume)
Built-in filter
Timer setup
(Wired remote controller)
Description
Type
AP009, AP012
AP015, AP018
Discharge
4-way
3-way
2-way
4-way
3-way
2-way
0000
Standard
2.7m
2.8m
3.0m
2.8m
3.2m
3.5m
(At shipment)
0001
High ceiling
�
—
—
—
3.2m
3.5m
3.8m
0003
High ceiling
�
—
—
—
3.5m
3.8m
—
Type
AP024 to AP030
AP036 to AP056
Discharge
4-way
3-way
2-way
4-way
3-way
2-way
0000
Standard
3.0m
3.3m
3.6m
3.0m
3.3m
3.6m
(At shipment)
0001
High ceiling
�
3.3m
3.5m
3.8m
3.3m
3.5m
3.8m
0003
High ceiling
�
3.6m
3.8m
—
3.6m
3.8m
—
0000: Standard filter (At shipment)
0000: Available (Operable)
0001: Unavailable (Operation prohibited)
At shipment
0000: Standard
0000: Available
TYPE
*1: Initial setting value of EEPROM installed on the service P.C. board
Indoor unit capacity
Setup data
*1 0001
Type
4-way Cassette
Abbreviated Model name
MMU-AP XXX HP
Setup data
0003
0005
0007
0009
0011
Model
009
012
015
018
024
Setup data
0012
0013
0015
0017
0018
Model
027
030
036
048
056
CODE No. [10]
∗
CODE No. [11]