– 53 –
FILE NO. SVM-
16041
Target outdoor unit (SMMS, SHRM, Mini-SMMS – Series 1 – 2)
CODE No.
Data
Format
Unit
Remote controller display example
00
01
02
03
04
05
08
0A
0B
0C
0D
Indoor unit
data
Individual
data 1 of
outdoor
unit *3
CODE No.
Data
Format
Unit
Remote controller display example
U1 U2 U3 U4
System unit
data
Room temperature (in control) *1
Room temperature (Remote controller)
Air Temperature (TA)
Coil Temperature (TCJ)
Coil Temperature (TC2)
Coil Temperature (TC1)
PMV
Number of connected indoor units
Total horse power of connected indoor units
Number of connected outdoor units
Total horse power of outdoor units
˚C
˚C
˚C
˚C
˚C
˚C
pls
—
HP
—
HP
[0024]=24 ˚C
[0050]=500 pls
[0048]=48
[0415]=41.5 HP
[0004]=4
[0420]=42 HP
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
Suction Temperature (TS)
Coil Temperature 1 (TE)
Liquid Temperature (TL)
Outdoor Temperature (TO)
Low-pressure saturation temperature (TU)
Current of compressor 1 (I1)
Current of compressor 2 (I2)
PMV1 + 2
PMV3
Compressor 1, 2 ON/OFF
Outdoor fan mode
Horse power of outdoor unit
*2
˚C
˚C
˚C
˚C
˚C
A
A
pls
pls
—
—
HP
[0024]=24 ˚C
[0135]=13.5 A
[0050]=500 pls
[0050]=500 pls
[0031]=Mode 31
[0016]=16HP
10 20 30 40
Discharge temperature of compressor 1
(Td1)
Discharge temperature of compressor 2
(Td2)
˚
C
11 21 31 41
˚
C
[0024]=24 ˚C
12 22 32 42
Detection pressure of high-pressure sensor
(Pd)
Detection pressure of low-pressure sensor
(Ps)
MPa
13 23 33 43
MPa
[0123]=1.23 MPa
*1 In the case of group connection, only the header indoor unit data can be displayed.
*2 01 ... Only compressor 1 is on
10 ... Only compressor 2 is on
11 ... Both compressor 1 and 2 are on
*3 The upper digit of CODE No. indicates the outdoor unit No.
U1 outdoor unit (Header unit)
U2 outdoor unit (follower unit 1)
U3 outdoor unit (follower unit 2)
U4 outdoor unit (follower unit 3)