– 25 –
FILE NO. SVM-
16041
No.
6
Item
Air speed selection
(Continued):
Outline of specifications
Remarks
Selection of high ceiling
type CODE No. :
[5d] or selection of high
ceiling on P.C. board SW501
3) In heating operation, the mode changes to [LL] if thermostat is turned off.
1. In heating operation, the higher temperature of
TC2 sensor and TCJ sensor is compared with
temperature of TC1 sensor and then the lower
temperature is used to set the upper limit of the
fan tap.
• When B zone has continued for 6 minutes,
the operation shifts to C zone.
• In defrost time, the control point is set to
+6°C.
TCJ: Temperature of indoor
heat exchanger sensor
• In D and E zones, priority
is given to remote control-
ler air speed setup.
• In A zone “ ” is displayed.
7
Prevention of cold air
discharge
E
B
A
A zone: OFF
B zone:
Over 26°C, below 28°C, ULTRA LOW (LL)
C zone:
Over 28°C, below 30°C, LOW (L)
D zone:
Over 30°C, below 32°C, MED (H)
E zone: HIGH (HH)
D
C
32
30
28
26
20
16
(°C)
CODE No.
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard
Type 1
Type 3
Type 6
0000
0001
0003
0006
OFF/OFF
ON/OFF
OFF/ON
ON/ON
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
HH
HH
HH
HH
HH
HH
H+
H+, H
H+, H
H+, H
H+, H
L+, L
L+, L
H+
HH
H
HH
H
L+
L+
H+
H+
L
L
H
L+
H
L+
L
L+
L
L+
L
L
LL
LL
LL
LL
LL
LL
LL
LL