Indoor service monitor list
* When the units are connected to a group, data of the header indoor unit only can be displayed.
** There is also a model which cannot be displayed.
• Refer to the service manual of an outdoor unit for "outdoor service monitor list".
CODE No.
Data name
Display format Unit
Remote control display example
Indoor unit data *
2
System data
00
01
02
03
04
05
06
08
F3
Room temperature (Use to control)
Room temperature (Remote control)
Indoor suction air temperature (TA)
Indoor coil temperature (TCJ)
Indoor coil temperature (TC2)
Indoor coil temperature (TC1)
Indoor discharge air temperature (TF) *
1
Indoor PMV opening
Filter sign time
×1
×1
×1
×1
×1
×1
×1
×1/10
×1
°C
°C
°F
°F
°F
°F
°F
pls
h
[0027] = 27 °
C
[0150]= 1500 pls
[2500] = 2500h
F9
Suction temperature of air to air heat
exchanger (TSA) *
1
×1
°F
[0080]= 80 °F
FA
0A
0B
0C
0D
Outside air temperature (TOA)*
1
No. of connected indoor units
Total horsepower of connected indoor units
No. of connected outdoor units
Total horsepower of outdoor units
×1
×1
×10
×1
×10
°F
unit
ton
unit
ton
[0048]= 48 units
[0215]= 21.5 ton
[0003]= 3 units
[0160]= 16 ton
[00
75
]=
75
°F
- 54 -