<RBC-AMS5*E-UL>
The position of indoor unit body by address
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
MENU] button
and the [
] button at the same time
to display the “Field setting menu”.
→
Push and hold the buttons for more than 4
seconds.
3
Push the [
] / [
] button to
select “7. DN setting” on the “Field setting
menu” screen, then push the “
S
et
Set” [
F2
F2] button.
4
Push the “
Unit
unit” [
F1
F1] button
to confirm the address of indoor unit.
→
The selected unit changes as follows each
time the button is pushed:
1-1
1-2
3
-
3
5
Push the “
S
et
Set” [
F2
F2] button.
→
The setting display for the selected unit
appears.
→
When the group control is used, the fan and
louver of the selected indoor unit operate.
6
Push the [
MENU] button to set the
other Code(DN) and Data. After
“Continue?” is displayed on the screen,
push the “
No
No” [
F2
F2] button
to finish the setting operation. “ Setting”
appears on the screen for a while, then
the screen returns to the “Field setting
menu” screen.
Field setting menu(2/2)
Return
Set
Setting timer operation mode
Setting timer operation mode
DN setting
DN setting
6.
7
.
8
.
Reset power consumption data
- 46 -