Installation diagram of Indoor and outdoor units
Before installing the
wireless remote controller
1. Remove the battery
cover.
2. Insert 2 new batteries
(R03 [AAA] type)
following the (+) and (−)
positions.
Wireless
remote controller
For the rear left and left piping
Do not allow the drain hose to get
slack.
Cut the piping
hole sloped
slightly.
Make sure to run the drain hose
sloped downward.
The auxiliary piping can be
connected to the left, rear left, rear
right, right, bottom right or bottom
left.
Insulate the refrigerant pipes
separately with insulation, not
together.
0.2"(6 mm) thick heat
resisting polyethylene foam
Right
Batteries
Flat head
wood screw
Wireless
remote controller
Remote control holder
Rear right
Rear
left
Bottom
right
Bottom left
Left
Insert the cushion between the
indoor unit and wall, and tilt the
indoor unit for better operation.
Cover
Wall
Installation
plate
Heat
insulator
Hook
*1
*2
Batteries
Installation space
The indoor unit shall be installed at least 8'2" (2.5 m) height.
Also it must be avoided to put anything on top of the indoor unit.
*1 Reserve space required to install the indoor unit and for service work.
Keep 4.3" (110 mm) or more for clearance between top plate of the indoor unit
and the ceiling surface.
*2 Provide a space as shown for service clearance for the cross flow fan.
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
• Direct sunlight to the indoor unit’s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner’s manual.)
Hook
Air filter
(Attach to the front
panel.)
11.8" (300 mm) or more
11.8" (300 mm) or
more
4.3" (1
10 mm) or more
Installation place
CAUTION
- 79 -