• For details about check codes determined with an Interface P.C. board or an Inverter P.C. board, refer to the Installation Manual of the outdoor unit.
*1 Inverter quantity information
(Super Modular Multi System i series (SMMS-i))
No.
Comp. Inverter
Fan
Inverter
Trouble
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
04
Comp. 3
05
Comp. 1 + Comp. 3
06
Comp. 2 + Comp. 3
07
Comp. 1 + Comp. 2 + Comp. 3
08
Fan
09
Comp. 1 + Fan
0A
Comp. 2 + Fan
0B
Comp. 1 + Comp. 2 + Fan
0C
Comp. 3 + Fan
0D
Comp. 1 + Comp. 3 + Fan
0E
Comp. 2 + Comp. 3 + Fan
0F
All
: Inverter trouble
*1 Inverter quantity information
(Super Modular Multi System e series (SMMS-e))
No.
Comp.
Inverter
Fan
Inverter
Trouble
1
2
1
2
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
08
Fan1
09
Comp. 1 + Fan1
0A
Comp. 2 + Fan1
0B
Comp. 1 + Comp. 2 + Fan1
10
Fan2
11
Comp. 1 + Fan2
12
Comp. 2 + Fan2
13
Comp. 1 + Comp. 2 + Fan2
18
Fan1 + Fan2
19
Comp. 1 + Fan1 + Fan2
1A
Comp. 2 + Fan1 + Fan2
1B
All
: Inverter trouble
Trouble detected by central control device
Check code
Wireless remote controller
Check code name
Judging
device
Central
control
device
indication
Outdoor unit 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation Timer Ready Flash
C05
─
─
─
Sending trouble in central control device
Communication
Link
C06
─
─
─
Receiving trouble in central control device
Communication
Link
C12
─
─
─
Batch alarm of general-purpose equipment
control interface
General-purpose
equipment I/F
P30
(L20)
Differs according to trouble contents of unit with occurrence of alarm
Group control follower unit trouble
Communication
Link
─
─
(L20 is displayed.)
• Duplication addresses of indoor units in
central control device
• With the combination of air conditioning
system, the indoor unit may detect the
check code of L20
Check code
Wireless remote controller
Check code name
Judging
device
Wired
remote
controller
display
Outdoor unit 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation Timer Ready Flash
P22
P22
#0: Element short circuit
#E: Vdc voltage trouble
#1: Position detection circuit trouble
#2: Input current sensor trouble
#3: Motor lock trouble
#C: Sensor temperature trouble
(No TH sensor)
#4: Motor current trouble
#D: Sensor short circuit/release
trouble (No TH sensor)
#5: Synchronization/step-out trouble
*Put in Fan Inverter No. in [#] mark.
ALT Outdoor unit fan inverter trouble
Inverter
P26
P26
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT IPM short protection trouble
Inverter
P29
P29
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT Comp. position detective circuit system
trouble
Inverter
P31
─
─
ALT Other indoor unit trouble
(Group follower indoor unit trouble)
Indoor unit
- 103 -
Summary of Contents for MMK-AP0157HPUL