No.
Part name
P
rocedure
s
Remarks
Electric part
box assembly
4
1) Follow the procedure item 3 .
2) Remove screw holding the electric part cover.
3) Take off the clamp base mounting screw and
then remove the clamp base assembly.
4) Take off fixing screws (2 pcs) of PMV
cover, and then remove PMV cover.
Screw
Clamp base assembly
Electric part cover
Screw
PMV cover fixing screw
PMV cover
Fan motor connector
Louver motor connector
PMV motor connector
Electric parts box
5) Pull out TC1, TC2, TCJ sensors from sensor
holder of hear exchanger.
(Pay attention to mounting positions of each
sensor when reassembling of electric parts. Be
sure to apply marking, etc to TC2 and TCJ
sensors before removing because their shapes
are reassembled.)
6) Remove the earth screw and earth line from
evaporator.
7) Disconnect the connectors for the fan motor,
louver motor and PMV motor from P.C. board
assembly.
8) Remove the 2 fixing screws that secures the
electric parts box assembly, unit display
assembly and remove the electric parts box
assembly.
Earth screw
TC2 sensor
TC1 sensor
TCJ sensor
Screw
Screw
Unit display
- 108 -
Summary of Contents for MMK-AP0157HPUL
Page 14: ...2 WIRING DIAGRAM 14 ...