Owner’s Manual

Air to Air Heat Exchanger with DX Coil Unit

Owner’s Manual

– 8 –

EN

5

How to Use

„

When using the remote controller for the Air to Air Heat 
Exchanger with DX Coil Unit (NRC-01HE) 

When you use the Air to Air Heat Exchanger with DX Coil Unit for the first time or change the settings, operate the 
remote following the procedure below.
From the next time, the unit starts running following the operation conditions you set by just pressing the 

 

button.

Preparation

Turning on the circuit breaker

When turned on, the separation lines appear and 

 blinks on the display of the remote controller.

* The remote controller will not work for about 1 minute after turning on the power. This is not a malfunction.
* To use a Air to Air Heat Exchanger with DX Coil Unit system linked with air conditioners, turn on the circuit 

breaker for the air conditioners too.

REQUIREMENT

• Keep the circuit breaker turned on during use.
• For the Air to Air Heat Exchanger with DX Coil Unit system linked with air conditioners, when the system is used after 

a long period of disuse, turn on the circuit breaker of the unit and air conditioners 12 hours or more before starting 
operation.

„

Operations

1

Press the 

 buttons to start operation. 

The operation lamp lights up.

REQUIREMENT

When the Air to Air Heat Exchanger with DX Coil Unit is 
in a system linked with air conditioners, they start 
running at the same time.

2

Push the “MODE 

” button to select a 

operation mode.

Each time the button is pushed, the operation 
mode and its icon change in the following order:

3

Press the 

 buttons to stop operation.

The operation lamp turns off.

„

Changing ventilation fan 
speed

1

Push the 

 button to select the ventilation 

fan speed. 

Each time the button is pushed, the speed and 
indication changes as follows.

* The indications 

 and 

 are 

displayed only when the air volume imbalance 
setting is activated.

REQUIREMENT

As factory default, the air volume imbalance setting is 
deactivated only [High] and [Low] are available for 
selection. Consult your dealer to activate the setting.

Heat

Dry

Cool

Fan

(Dehumidify)

High

Low

SA>EA (SA<EA)

About air volume imbalance (

 

[SA>EA]/

 [SA<EA])

For normal ventilation (High or Low): 

The volumes of the indoor air supply and outdoor air 
exhaustion are set to the same level.

For volume ventilation imbalance: 

• When 

 

[SA>EA] is selected: the volume of the 

indoor air supply is larger than that of the outdoor air 
exhaustion.
(Inflow of humidity and smells from the toilet and 
kitchen is reduced.)

• When 

 

[SA<EA] is selected: the volume of the 

outdoor air exhaustion is larger than that of the 
indoor air supply.
(Outflow of smells and floating bacteria into a 
corridor or other places is reduced.

* Consult your dealer if the setting of the air volume 

imbalance seems incorrect.

„

Changing ventilation mode

1

Push the 

 button to select a ventilation 

mode.

Each time the button is pushed, the ventilation 
mode and indication change as follows:

About ventilation modes

The unit has two ventilation modes.

Automatic mode

The heat exchange mode and the bypass mode* are 
automatically switched between according to the 
operation mode (cooling, heating, dry, ventilation), 
setting temperature, or information from the indoor/
outdoor thermo sensor of the Air to Air Heat 
Exchanger with DX Coil Unit.

Heat exchange mode

Exchanging heat between the outdoor and indoor air 
and making the temperature and humidity of the 
outdoor air closer to those of the indoor air before 
supplying it.

*

Bypass mode (unavailable)

Outdoor air is taken into a room as it is. This mode is 

mainly used in spring and summer.

CAUTION

If the outdoor temperature falls to 15°C or below in 
[Automatic mode] the system will automatically start to 
run in [Heat exchange mode] regardless of the mode 
setting to prevent condensation in the Air to Air Heat 
Exchanger with DX Coil Unit.

* The indication of the ventilation mode setting does not 

change.

„

Changing the set temperature

1

Push the “TEMP. 

 

” buttons.

Push 

 to increase the temperature, and 

 to 

decrease the temperature. (The set temperature 
cannot be changed in the fan mode.) 

„

About the separate operation 
of the Air to Air Heat 
Exchanger with DX Coil Unit 
in a system linked with air 
conditioners

* The procedure below is not effective in a system 

equipped with the Air to Air Heat Exchanger with DX 

Coil Unit only.

1

Press the 

 button while the system is 

running.

Only the Air to Air Heat Exchanger with DX Coil 
Unit stops and the 

 indicator turns off.

2

Press the 

 button while the system is 

stopped.

The 

 indicator lights up and the Air to Air Heat 

Exchanger with DX Coil Unit starts running 
separately.

NOTE

• Normally, the Air to Air Heat Exchanger with DX Coil 

Unit ON/OFF as the air conditioner is ON/OFF when it 
is in a system linked with air conditioners.

• If “

” is displayed when the 

 button is pushed, 

change certain settings is necessary to operate the 
unit separately. Consult your dealer to change the 
settings.

Automatic mode

Heat exchange 

mode

15-EN

16-EN

+00ET99915201_00Ta.book  Page 8  Tuesday, February 15, 2011  6:45 PM

Summary of Contents for MMD-VN1002HEX1E

Page 1: ...Coil Unit Model name Model with a humidifier MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE Model without a humidifier MMD VN502HEXE MMD VN802HEXE MMD VN1002HEXE Owner s Manual For commercial use Owner s Manual 1 English 00ET99915201_00Ta book Page 1 Tuesday February 15 2011 6 45 PM ...

Page 2: ...roughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigeran...

Page 3: ...g installation servicing and removal Use of a stand more than 50 cm high to clean the filter of the Air to Air Heat Exchanger with DX Coil Unit or to carry out other such jobs constitutes working at heights Due to the danger of falling off the stand and injuring yourself while working at heights this kind of work should not be done by unqualified individuals When this kind of work must be carried ...

Page 4: ...erson 1 to refit the unit Do not set the circuit breaker to the ON position until the unit has been refitted Do not move or repair any unit by yourself Since there is high voltage inside the unit you may get electric shock when removing the cover and main unit Do not modify the products Do not also disassemble or modify the parts It may cause a fire electric shock or injury Relocation When the Air...

Page 5: ...ndle with packing band or may get injured in case of broken band 2 cartons 91 kg 2 Part Names Air to Air Heat Exchanger with DX Coil Unit Separately sold parts Remote controller for the Air to Air Heat Exchanger with DX Coil Unit NRC 01HE SA Supply air RA Return air EA Exhaust air OA Outdoor air Inspection cover for the heat exchange element Earth screw in electrical control box Drain hole Connect...

Page 6: ...X Coil Unit Outdoor unit Remote controller NRC 01HE RBC AMT32E Air conditioner Air conditioner Air to Air Heat Exchanger with DX Coil Unit Air to Air Heat Exchanger with DX Coil Unit When the Air to Air Heat Exchanger with DX Coil Unit system linked with indoor air conditioners is used set the Air to Air Heat Exchanger with DX Coil Unit as Follower referring to Setting the address manually using t...

Page 7: ...he remote controller display after pushing the button 5 button Filter reset button Resets FILTER indication after cleaning 6 button Power save operation Use to initiate power saving mode Display section Operation section 1 3 5 2 6 4 7 button Swing Louver direction button 1 8 Operation lamp Lights up during operation Blinks when an error occurs or the protective device activates 9 button Turns on t...

Page 8: ... mode 17 Louver lock indicator 1 18 UNIT No indicator The number of the Air to Air Heat Exchanger with DX Coil Unit selected using the UNIT button or that of the unit in which an error has occurred 19 Central control indicator Displayed when a central control device such as a central controller is also used If the central control device prohibits the use of local remote controllers blinks when any...

Page 9: ... the outdoor air exhaustion Inflow of humidity and smells from the toilet and kitchen is reduced When SA EA is selected the volume of the outdoor air exhaustion is larger than that of the indoor air supply Outflow of smells and floating bacteria into a corridor or other places is reduced Consult your dealer if the setting of the air volume imbalance seems incorrect Changing ventilation mode 1 Push...

Page 10: ...mount of time has passed between the nighttime heat purge operation becoming on standby and the monitoring operation starting The time is set between 1 48 hours in 1 hour steps 2 The indoor temperature is 3 C or more higher than the outdoor temperature and the indoor temperature is 2 C or more higher than the temperature set for the operation The conditions to pause the nighttime heat purge operat...

Page 11: ...s Hours 7 Installation Location Do not install the unit in places where the outside temperature falls below 5 C Avoid installing near machines emitting high frequency waves Not suitable for chemical plants such as liquefied carbon dioxide refrigerant plants A failure may occur in certain locations such as the following Areas with large amount of oil droplets including machine oil or vapors Salty a...

Page 12: ...et of the indoor unit is blocked NOTE When the protective device activates turn off the power switch remove the cause and then restart running Cooling Heating operations Each unit can be controlled individually However indoor units connected to the same outdoor unit cannot perform cooling and heating simultaneously When you attempt simultaneous operation indoor units performing cooling are stopped...

Page 13: ...t exchanger etc expand and contract slightly due to change of temperature indication is lit When cooling operation cannot be performed because another indoor unit performs heating operation Is outdoor temperature out of operation temperature range indication is lit When the manager of the Air to Air Heat Exchanger with DX Coil Unit has fixed the operation to COOL or HEAT and an operation contrary ...

Page 14: ...the indoor unit will be deleted 3 After confirmation push button to return to the usual display Check code Indoor unit No in which an error occurred 3 2 1 11Specifications Model with a humidifier Model without a humidifier Sound Power Level is less than 70 dBA MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE MMD VNK1002HEXE2 Type Function Cooling and heating dual purpose type Unit configuration Discr...

Page 15: ...chinery described below Generic Denomination Air conditioner Air to Air Heat Exchanger with DX Coil Unit Model type MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE MMD VNK1002HEXE2 MMD VN502HEXE MMD VN802HEXE MMD VN1002HEXE MMD VN1002HEXE2 Commercial name TOSHIBA Air to Air Heat Exchanger with DX Coil Unit Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulatio...

Page 16: ...CARRIER CORPORATION Address city country 336 Tadehara Fuji shi Shizuoka ken 416 8521 Japan Name of the Importer Distributor in EU Toshiba Carrier UK Ltd Address city country Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom 00ET99915201_00Ta book Page 29 Tuesday February 15 2011 6 45 PM ...

Reviews: