Air to Air Heat Exchanger with DX Coil Unit

Owner’s Manual

Air to Air Heat Exchanger with DX Coil Unit

Owner’s Manual

– 9 –

 About nighttime heat purge operation

• Nighttime heat purge is a function to reduce the 

room air conditioning load in the morning in 
summer by exhausting the air indoor which has 
become warm while the air conditioner is 
stopped in the night automatically in the Bypass 
mode.

The nighttime heat purge operation functions if 
night purge is activated and the last operation 
mode of the air conditioner before stopping is 

 or 

 in an Air to Air Heat Exchanger 

with DX Coil Unit system linked with air 
conditioners.

If the 

 button is pushed while the system is 

running, the operation lamp turns off, 

 appears on 

the display, and the nighttime heat purge operation 
turns on-standby. 
After the operation becomes on-standby, the unit 
automatically starts ventilation in [Low] ventilation 
fan speed and [Bypass mode] when the conditions to 
start the nighttime heat purge operation below are 
fulfilled.
The nighttime heat purge operation is paused for one 
hour if any of the conditions to pause the operation 
are detected.
If the conditions to start the nighttime heat purge 
operation are fulfilled one hour after the pause, the 
operation will start again. If not, the operation will 
remain paused for one more hour. 
This cycle is repeated until the conditions to stop 
(end) the nighttime heat purge operation below are 
fulfilled. 

NOTE

• The setting of the nighttime heat purge operation is 

“OFF” As factory default.
Consult your dealer to change the setting to “ON” or 
the setting of the time until the monitoring operation 
starts.

• The settings of 

 or 

 cannot be changed during 

the nighttime heat purge operation. Their indicators 
are not displayed.

• The 

 indicator stays lit while the operation is on-

standby or paused.

• The nighttime heat purge operation cannot be 

activated if 24-hour ventilation is activated.

CAUTION

The nighttime heat purge operation is not executed if the 
outdoor temperature becomes about 15°C or less to 
prevent condensation in the Air to Air Heat Exchanger 
with DX Coil Unit, but the 

 indicator is still lit. 

The conditions to start the nighttime heat purge 
operation

The unit compares temperatures indoor and outdoor 
using the monitoring operation (for about 5 minutes) 
and will start the nighttime heat purge operation if the 
following conditions are fulfilled.
1. A certain amount of time has passed between the 

nighttime heat purge operation becoming on-
standby and the monitoring operation starting. (The 
time is set between 1- 48 hours in 1 hour steps.)

2. The indoor temperature is 3°C or more higher than 

the outdoor temperature and the indoor 
temperature is 2°C or more higher than the 
temperature set for the operation.

The conditions to pause the nighttime heat purge 
operation (the operation pauses for one hour.)

1. The indoor temperature is the same or lower than 

the outdoor temperature, the indoor temperature is 
the same or lower than the temperature set for the 
operation, or one hour has passed since the 
nighttime heat purge operation started.

The conditions to stop (end) the nighttime heat 
purge operation

The nighttime heat purge operation ends and the 

 

indicator disappears if any of the following conditions 
are fulfilled.
1. The air conditioner or Air to Air Heat Exchanger 

with DX Coil Unit is started.

2. 48 hours has passed since the monitoring 

operation started.

About humidifying

Humidifying is available during heating.

REQUIREMENT

• When the humidifying season is over, perform the 

drying operation for the humidifier.
Even during humidifying season, perform the drying 
operation if the unit is not used for a long period of time 
(over a couple of weeks).
The drying operation must be performed in ventilation 
mode for over 24 hours.
Failure to perform the drying operation may cause 
residual water to rot down and emit an unpleasant 
odor.

• It is required to replace the humidifying element if it 

emits such an odor.

• During humidifying season, when running only this 

unit while all the other air-conditioners in the room are 
stopped, change the heating mode to the ventilation 
mode, and stop the humidifying operation. Continuing 
the humidifying operation may increase the 
temperature and create condensation.

To use the Air to Air Heat Exchanger with DX Coil 
Unit effectively, observe the following conditions.

* If the Air to Air Heat Exchanger with DX Coil Unit is 

continuously operated beyond the conditions above, 

the protective device will be activated and force the 

unit to stop.

Cooling 

operation

Outdoor temperature 

range

-5°C to +43°C

Room temperature 

range

+21°C to +32°C

Room humidity

80% or less

If the Air to Air Heat Exchanger with DX Coil 

Unit continues running for a long time with the 

room humidity over 80%, water droplets may 

fall from the unit or may be emitted from the air 

outlet.

Heating 

operation

Outdoor temperature 

range

-15°C to +21°C

Room temperature

+28°C or less

17-EN

18-EN

+00ET99915201_00Ta.book  Page 9  Tuesday, February 15, 2011  6:45 PM

Summary of Contents for MMD-VN1002HEX1E

Page 1: ...Coil Unit Model name Model with a humidifier MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE Model without a humidifier MMD VN502HEXE MMD VN802HEXE MMD VN1002HEXE Owner s Manual For commercial use Owner s Manual 1 English 00ET99915201_00Ta book Page 1 Tuesday February 15 2011 6 45 PM ...

Page 2: ...roughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigeran...

Page 3: ...g installation servicing and removal Use of a stand more than 50 cm high to clean the filter of the Air to Air Heat Exchanger with DX Coil Unit or to carry out other such jobs constitutes working at heights Due to the danger of falling off the stand and injuring yourself while working at heights this kind of work should not be done by unqualified individuals When this kind of work must be carried ...

Page 4: ...erson 1 to refit the unit Do not set the circuit breaker to the ON position until the unit has been refitted Do not move or repair any unit by yourself Since there is high voltage inside the unit you may get electric shock when removing the cover and main unit Do not modify the products Do not also disassemble or modify the parts It may cause a fire electric shock or injury Relocation When the Air...

Page 5: ...ndle with packing band or may get injured in case of broken band 2 cartons 91 kg 2 Part Names Air to Air Heat Exchanger with DX Coil Unit Separately sold parts Remote controller for the Air to Air Heat Exchanger with DX Coil Unit NRC 01HE SA Supply air RA Return air EA Exhaust air OA Outdoor air Inspection cover for the heat exchange element Earth screw in electrical control box Drain hole Connect...

Page 6: ...X Coil Unit Outdoor unit Remote controller NRC 01HE RBC AMT32E Air conditioner Air conditioner Air to Air Heat Exchanger with DX Coil Unit Air to Air Heat Exchanger with DX Coil Unit When the Air to Air Heat Exchanger with DX Coil Unit system linked with indoor air conditioners is used set the Air to Air Heat Exchanger with DX Coil Unit as Follower referring to Setting the address manually using t...

Page 7: ...he remote controller display after pushing the button 5 button Filter reset button Resets FILTER indication after cleaning 6 button Power save operation Use to initiate power saving mode Display section Operation section 1 3 5 2 6 4 7 button Swing Louver direction button 1 8 Operation lamp Lights up during operation Blinks when an error occurs or the protective device activates 9 button Turns on t...

Page 8: ... mode 17 Louver lock indicator 1 18 UNIT No indicator The number of the Air to Air Heat Exchanger with DX Coil Unit selected using the UNIT button or that of the unit in which an error has occurred 19 Central control indicator Displayed when a central control device such as a central controller is also used If the central control device prohibits the use of local remote controllers blinks when any...

Page 9: ... the outdoor air exhaustion Inflow of humidity and smells from the toilet and kitchen is reduced When SA EA is selected the volume of the outdoor air exhaustion is larger than that of the indoor air supply Outflow of smells and floating bacteria into a corridor or other places is reduced Consult your dealer if the setting of the air volume imbalance seems incorrect Changing ventilation mode 1 Push...

Page 10: ...mount of time has passed between the nighttime heat purge operation becoming on standby and the monitoring operation starting The time is set between 1 48 hours in 1 hour steps 2 The indoor temperature is 3 C or more higher than the outdoor temperature and the indoor temperature is 2 C or more higher than the temperature set for the operation The conditions to pause the nighttime heat purge operat...

Page 11: ...s Hours 7 Installation Location Do not install the unit in places where the outside temperature falls below 5 C Avoid installing near machines emitting high frequency waves Not suitable for chemical plants such as liquefied carbon dioxide refrigerant plants A failure may occur in certain locations such as the following Areas with large amount of oil droplets including machine oil or vapors Salty a...

Page 12: ...et of the indoor unit is blocked NOTE When the protective device activates turn off the power switch remove the cause and then restart running Cooling Heating operations Each unit can be controlled individually However indoor units connected to the same outdoor unit cannot perform cooling and heating simultaneously When you attempt simultaneous operation indoor units performing cooling are stopped...

Page 13: ...t exchanger etc expand and contract slightly due to change of temperature indication is lit When cooling operation cannot be performed because another indoor unit performs heating operation Is outdoor temperature out of operation temperature range indication is lit When the manager of the Air to Air Heat Exchanger with DX Coil Unit has fixed the operation to COOL or HEAT and an operation contrary ...

Page 14: ...the indoor unit will be deleted 3 After confirmation push button to return to the usual display Check code Indoor unit No in which an error occurred 3 2 1 11Specifications Model with a humidifier Model without a humidifier Sound Power Level is less than 70 dBA MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE MMD VNK1002HEXE2 Type Function Cooling and heating dual purpose type Unit configuration Discr...

Page 15: ...chinery described below Generic Denomination Air conditioner Air to Air Heat Exchanger with DX Coil Unit Model type MMD VNK502HEXE MMD VNK802HEXE MMD VNK1002HEXE MMD VNK1002HEXE2 MMD VN502HEXE MMD VN802HEXE MMD VN1002HEXE MMD VN1002HEXE2 Commercial name TOSHIBA Air to Air Heat Exchanger with DX Coil Unit Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulatio...

Page 16: ...CARRIER CORPORATION Address city country 336 Tadehara Fuji shi Shizuoka ken 416 8521 Japan Name of the Importer Distributor in EU Toshiba Carrier UK Ltd Address city country Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom 00ET99915201_00Ta book Page 29 Tuesday February 15 2011 6 45 PM ...

Reviews: