– 59 –
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check code
Sub-code
E31
E31
Symbol O
signifies site of
IPDU error.
I/F
IPDU
communication
error
All stop
Communication is disrupted
between IPDUs (P.C.
boards) in inverter box.
• Check wiring and
connectors involved in
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
• Check for defect in outdoor
P.C. board (I/F, A3-IPDU
or Fan IPDU).
• Check for external noise.
F01
–
–
Indoor
unit
Indoor TCJ
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TCJ
sensor connector and
wiring.
• Check resistance
characteristics of TCJ
sensor.
• Check for defect in indoor
P.C. board.
F02
–
–
Indoor
unit
Indoor TC2
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TC2
sensor connector and
wiring.
• Check resistance
characteristics of TC2
sensor.
• Check for defect in indoor
P.C. board.
F03
–
–
Indoor
unit
Indoor TC1
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
F04
F04
–
I/F
TD1 sensor
error
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
F05
F05
–
I/F
TD2 sensor
error
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
F06
F06
01:
TE1 sensor error
02:
TE2 sensor error
I/F
TE1/TE2
sensor error
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
F07
F07
–
I/F
TL sensor error All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL
sensor.
• Check for defect in outdoor
P.C. board (I/F).