9-2. Troubleshooting Method
The remote controllers (main remote controller and central control remote controller) and the interface P.C. board
of an outdoor unit are provided with an LCD display (remote controller) or a 7-segment display (outdoor interface
P.C. board) to display operational status. Using this self-diagnosis feature, the fault site/faulty part may be identified
in the event of a fault by following the method described below.
The list below summarizes check codes detected by various devices. Analyze the check code according to where it is displayed and work out
the nature of the fault in consultation with the list.
• When investigating a fault on the basis of a display provided on the indoor remote controller or TCC-LINK central control remote controller -
See the “TCC-LINK remote control or main remote controller display” section of the list.
• When investigating a fault on the basis of a display provided on an outdoor unit - See the “Outdoor 7-segment display” section of the list.
• When investigating a fault on the basis of a wireless remote controller-controlled indoor unit - See the “Light sensor indicator light block”
section of the list.
List of Check Codes (Indoor Unit)
(Error detected by indoor unit)
Check code
Display of receiving unit
Typical fault site
Description of error
TC
C-LINK central
control or main remote
controller display
Outdoor 7-segment display
Indicator light block
Sub-c ode
Flash
E03
–
–
Indoor-remote controller periodic
communication error
Communication from remote controller or network
adaptor has been lost (so has central control
communication).
E04
–
–
Indoor-outdoor periodic
communication error
Signals are not being received from outdoor unit.
E08
E08 Duplicated indoor address
Duplicated indoor address
Indoor unit detects address identical to its own.
E10
–
–
Indoor inter-MCU communication
error
MCU communication between main controller and
motor microcontroller is faulty.
E18
–
–
Error in periodic communication
between indoor header and
follower unit
Periodic communication between indoor header
and follower units cannot be maintained.
F01
–
–
ALT
Indoor heat exchanger
temperature sensor (TCJ) error
Heat exchanger temperature sensor (TCJ) has
been open/short-circuited.
F02
–
–
ALT
Indoor heat exchanger
temperature sensor (TC2) error
Heat exchanger temperature sensor (TC2) has
been open/short-circuited.
F03
–
–
ALT
Indoor heat exchanger
temperature sensor (TC1) error
Heat exchanger temperature sensor (TC1) has
been open/short-circuited.
F10
–
–
ALT
Ambient temperature sensor (TA)
error
Ambient temperature sensor (TA) has been open/
short-circuited.
F11
–
–
ALT
Discharge temperature sensor
(TF) error
Discharge temperature sensor (TF) has been open/
short-circuited.
F29
–
–
SIM P.C. board or other indoor error
Indoor EEPROM is abnormal (some other error may
be detected).
L03
–
–
SIM
Duplicated indoor group header
unit
There is more than one header unit in group.
L07
–
–
SIM
Connection of group control cable
to stand-alone indoor unit
There is at least one stand-alone indoor unit to
which group control cable is connected.
L08
L08
–
SIM Indoor group address not set
Address setting has not been performed for one or
more indoor units (also detected at outdoor unit
end).
L09
–
–
SIM Indoor capacity not set
Capacity setting has not been performed for indoor
unit.
L20
–
–
SIM Duplicated central control address
There is duplication in central control address
setting.
L30
L30 Detected indoor unit No.
SIM
Indoor external error input
(interlock)
Unit shutdown has been caused by external error
input (CN213)
P01
–
–
ALT Indoor AC fan error
Indoor AC fan error is detected (activation of fan
motor thermal relay).
P31
–
–
ALT Other indoor unit error
Follower unit cannot be operated due to header unit
alarm (E03/L03/L07/L08).
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Lighting,
: Flashing,
: Goes off
ALT.: Flashing is alternately when there are two flashing LED