– 16 –
No.
1
2
3
Room temp.
control
Item
When power
supply is reset
Operation
mode selection
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
3) If resetting the power supply during occurrence of a trouble,
the check code is once cleared. After ON/OFF button of the
remote controller was pushed and the operation was re-
sumed, if the abnormal status continues, the check code is
again displayed on the remote controller.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
1) Adjustment range: Remote controller setup temperature (°F [°C] )
Remarks
Air speed (rpm)/
Air direction adjustment
Wired type
Wireless type
COOL/DRY
64°F [18°C] to 84°F [29°C]
64°F [18°C] to 86°F [30°C]
HEAT
64°F [18°C] to 84°C [29°C]
61°F [16°C] to 86°F [30°C]
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Setting at shipment
Shift of suction
temperature in heating
operation
Except while sensor of
the remote controller is
controlled
(Code No. [32], “0001”)
Setup data
2
Remote controller
command
STOP
FAN
DRY
COOL
HEAT
Control outline
Air conditioner stops.
Fan operation
Drying operation
Cooling operation
Heating operation
Setup data
Setup temp.
Correction
0
2
4
6
+0°F
+3.6°F
+7.2°F
+10.8°F
[+0°C]
[+2°C]
[+4°C]
[+6°C]
7. CONTROL OUTLINE