– 32 –
Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN
Item
Descrip tio n
At sh ip men t
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
According to type
02
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
03
Central control address
0001: No.1 unit
0099: Unfixed
to
0064: No.64 unit
0099: Unfixed
04
Specific indoor unit
priority
0000: No priority
0001: Priority
0000: No priority
06
Heating temp shift
0000: No shift
0002: +2˚C(+3.6˚F)
to
0001: +1˚C(+1.8˚F)
0010: +10˚C(+18˚F)
(Up to +6 recommended)
0002: +2˚C(+3.6˚F)
(Floor type 0000: 0˚C)
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
0F
Cooling only
0000: Heat pump
0001: Cool
0006: High static Ducted Type
ing only (No display of [AUTO] [HEAT])
0000: Heat pump
10
Type
11
Indoor unit capacity
0000: Unfixed
0001 to 0034
According to capacity
type
12
Line address
0001: No.1 unit
to
0030: No.30 unit
0099: Unfixed
13
Indoor unit address
0001: No.1 unit
to
0064: No.64 unit
0099: Unfixed
14
Group address
0000: Individual
0002: Follower unit of group
0001: Header unit of group
0099: Unfixed
28
Automatic restart of
power failure
0000: None
0001: Restart
0001: Restart
2A
Selection of option/error
input (CN213)
0000: Filter input
0002: External interlock
0001: Alarm input (Option parts)
0002: External interlock
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
31
Ventilating fan control
0000: Unavailable
0001: Available
0000: Unavailable
32
TA sensor selection
0000: Body TA sensor
0001: Remote controller sensor
0000: Body TA sensor
33
Temperature unit select
0000: ˚C
: (at factory shipment)
0001: ˚F
0001:
:
˚F
60
Timer setting
(wired remote controller)
0000: Available (can be performed)
0001: Unavailable (cannot be performed)
0000: Available
92
Outside interlock
release condition
0000: Operation stop
0001: Release com munica tion signal receive
0000: Operation stop
According to model
type
Type
DN code “10”
*1 Default value stored in EEPROM mounted on service P.C. board
Indoor Unit Capacity
DN code “11”
*1 Default value stored in EEPROM
mounted on service P.C. board
Value
Type
Model
Value
Capacity
0000*
Invalid
0021
072 type
0006
High static Ducted
MMD-AP
***
H2UL
0023
096 type
~
–