![Toshiba MMC-P0151H Design Manual Download Page 70](http://html.mh-extra.com/html/toshiba/mmc-p0151h/mmc-p0151h_design-manual_423774070.webp)
1-68
0.5
294
245
196
147
98
49
0
1
1.5
2
MMD-P0181H
Current of f
an motor (A)
Standard air volume : 900m³/h
Exter
nal static pressure (P
a)
720
1080
High static pressure tap
High static pressure tap
Medium static
pressure tap
Medium static
pressure tap
Medium static
pressure tap
Medium static
pressure tap
Low static pressure tap
Low static pressure tap
0.5
294
245
196
147
98
49
0
1
1.5
2
MMD-P0361H
Current of f
an motor (A)
Standard air volume : 1600m³/h
Exter
nal static pressure (P
a)
1280
1920
High static pressure tap
High static pressure tap
Medium static pressure tap
Low static pressure tap
Low static pressure tap
0.5
294
245
196
147
98
49
0
1
1.5
2
MMD-P0241H
Current of f
an motor (A)
Standard air volume : 1320m³/h
Exter
nal static pressure (P
a)
1056
1584
High static pressure tap
High static pressure tap
Medium static
pressure tap
Low static pressure tap
Low static pressure tap
0.5
294
245
196
147
98
49
0
1
1.5
2
MMD-P0481H
Current of f
an motor (A)
Standard air volume : 2100m³/h
Exter
nal static pressure (P
a)
1680
2520
700
800
900
1000
1100
Air volume (m³/h)
1200
1400
1600
1800
2000
Air volume (m³/h)
1000
1100
1200
1300
1400
1500
1600
Air volume (m³/h)
1600
1800
2000
2200
2400
2600
Air volume (m³/h)
High static pressure tap
High static pressure tap
Medium static
pressure tap
Medium static
pressure tap
Low static pressure tap
Low static pressure tap
Lower limit
of air volume
Upper limit
of air volume
Lower limit
of air volume
Upper limit
of air volume
Lower limit
of air volume
Upper limit
of air volume
Lower limit
of air volume
Upper limit
of air volume
• Concealed Duct High Static Pressure type
(TENTATIVE)