1-4. EQUIPMENT SELECTION PROCEDURE
1. Selection flow chart
2. Combination conditions for indoor unit and outdoor unit
1. For indoor unit, the capacity code is decided for each capacity rank.
1. Determination of indoor load
2. Preliminary selection of indoor
3. Preliminary selection of outdoor unit with indoor units
4. Capacity correction for piping length/distance between indoor and outdoor units
5. Capacity correction based on indoor and outdoor temperature
6. Validate preliminary selection of indoor units
7. Confirmation of selection for indoor unit and outdoor units
End
NO
Outdoor unit
(Cooling only)
Outdoor unit
(Heat pump)
Outdoor unit
(Heat pump)
Capacity code of
outdoor unit
Max. No. of
indoor units
Total capacity code
of indoor units
MMY-MP0801T8
MMY-MP0801HT8
MMY-MP0801HT7
8
13
4 to 10.8
MMY-MP1001T8
MMY-MP1001HT8
MMY-MP1001HT7
10
16
5 to 13.5
MMY-P1401T8
MMY-P1401HT8
MMY-P1401HT7
14
16
7 to 18.9
MMY-P1601T8
MMY-P1601HT8
MMY-P1601HT7
16
18
8 to 21.6
MMY-P1801T8
MMY-P1801HT8
MMY-P1801HT7
18
18
9 to 24.3
MMY-P2001T8
MMY-P2001HT8
MMY-P2001HT7
20
20
10 to 27
MMY-P2201T8
MMY-P2201HT8
MMY-P2201HT7
22
22
11 to 29.7
MMY-P2401T8
MMY-P2401HT8
MMY-P2401HT7
24
24
12 to 32.4
MMY-P2601T8
MMY-P2601HT8
MMY-P2601HT7
26
26
13 to 35.1
MMY-P2801T8
MMY-P2801HT8
MMY-P2801HT7
28
28
14 to 37.8
MMY-P3001T8
MMY-P3001HT8
MMY-P3001HT7
30
30
15 to 40.5
MMY-P3201T8
MMY-P3201HT8
MMY-P3201HT7
32
32
16 to 43.2
MMY-P3401T8
MMY-P3401HT8
MMY-P3401HT7
34
34
17 to 45.9
MMY-P3601T8
MMY-P3601HT8
MMY-P3601HT7
36
36
18 to 48.6
MMY-P3801T8
MMY-P3801HT8
MMY-P3801HT7
38
38
19 to 51.3
MMY-P4001T8
MMY-P4001HT8
MMY-P4001HT7
40
40
20 to 54.0
MMY-P4201T8
MMY-P4201HT8
MMY-P4201HT7
42
40
21 to 56.7
MMY-P4401T8
MMY-P4401HT8
MMY-P4401HT7
44
40
22 to 59.4
MMY-P4601T8
MMY-P4601HT8
MMY-P4601HT7
46
40
23 to 62.1
NOTE :
Capacity rank : Correspondence to Btu/h.
Capacity code : Correspondence to Horsepower.
2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
50 to 135 % of outdoor unit capacity
Capacity rank
Type
Capacity code
007
0.8
009
1
012
1.25
015
1.7
018
2
024
2.5
030
3.2
036
4
048
5
072
8
096
10