28 I
TOSHIBA
28 I
TOSHIBA
0-10 V interface [HWS-IFAIP01U-E] (optional)
For connecting the 0-10 V interface
TB04 for wiring the 0-10 V interface to the E-BOX of the hydro unit
• Use 2-wire, non-polarized lines for the communication line.
• Use 2-wire shielded lines to prevent faults.
• In this case, close (connect) the ends of the shielded lines and
insulate the end of the terminal in order to ground the system.
• Make sure that no more than DC10 V is applied to the analog input inlays.
• The remote control line (AB line) can establish a connection to a maximum of 2 units. Main control
plus second remote control or KNX or MODBUS or WLAN adapter or 0-10 V control.
For example, main control plus second remote control or KNX or MODBUS or WLAN adapter or
0-10 V control.
This option enables either the set temperatures or the capacity to be controlled .
Control of the set temperature
• DN 680 is set to "1".
• Define the input method for each set temperature.
DN
Point
Selectable value (input of)
681
Set hot water temperature
0: AI not used
1: AI1
2: AI 2
3: AI 3
682
Zone 1 set temperature for heating.
0: AI not used
1: AI1
2: AI 2
3: AI 3
683
Zone 2 set temperature for heating.
0: AI not used
1: AI1
2: AI 2
3: AI 3
684
Zone 1 set temperature for cooling.
0: AI not used
1: AI1
2: AI 2
3: AI 3
• Set the temperature from 0 to 10 V and define its accuracy.
*( ): HWT-110
DN
Point
Selectable value
685
Upper limit value of the set hot water temperature
(at voltage level 16)
40 to 80
Default: 65°C
689
Accuracy of the set hot water temperature
(value at voltage level)
1 to 5
Default: 5°C
686
Upper limit of the set temperature in Zone 1 for
heating (at voltage level 16)
20 to 55 (65)
Default: 55°C
68A
Accuracy of the set temperature in Zone 1 for
heating (value at voltage level)
1 to 5
Default: 3°C
687
Upper limit of the set temperature in Zone 2 for
heating (at voltage level 16)
20 to 55 (65)
Default: 55°C
68B
Accuracy of the set temperature in Zone 2 for
heating (value at voltage level)
1 to 5
Default: 3°C
688
Upper limit of the set temperature in Zone 1 for
cooling (at voltage level 16)
7 to 25
Default: 20°C
68C
Accuracy of the set temperature in Zone 1 for
cooling (value at voltage level)
1 to 5
Default: 1°C
– 18 –
Hydro Unit
Installation Manual
■
0-10V interface [HWS-IFAIP01U-E] (option)
To connect the 0-10V interface
TB04 for the 0-10V interface wiring on the Hydro Unit E-BOX
• Communication wiring use 2-core non-polarity wires.
• Use 2-core shield wires to prevent noise trouble.
• In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
• Be sure not input more than DC10V to the analogue input terminals.
• The remote controller line (AB line) is available to connect maximum 2 units.
For example the header plus second remote controller or the KNX or the MODBUS or the Wireless Adapter or
the 0-10V controller.
This option allows Hydro Unit to be controlled either Setting temperatures or Capacity.
Control of Setting tempareture
• DN 680 is set to "1".
• Set the input method for each setting temperature.
• Allocate the temperature of 0 to 10V, and also set its resolution.
*( ): HWT-110
DN
Item
Selectable value (Input from)
681
Hot water setting temperature.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
682
Zone 1 setting temperature for heating.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
683
Zone 2 setting temperature for heating.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
684
Zone 1 setting temperature for cooling.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
RC : Remote controller
DN
Item
Selectable value
685
Upper limit of hot water setting temp.
(at voltage level 16)
40 to 80
Default: 65°C
689
Resolution of hot water setting temp.
(Value per voltage level)
1 to 5
Default: 5°C
686
Upper limit of Zone 1 setting temperature for heating
(at voltage level 16)
20 to 55 (65)
Default: 55°C
68A
Resolution of Zone 1 setting temperature for heating
(Value per voltage level)
1 to 5
Default: 3°C
687
Upper limit of Zone 2 setting temperature for heating
(at voltage level 16)
20 to 55 (65)
Default: 55°C
68B
Resolution of Zone 2 setting temperature for heating
(Value per voltage level)
1 to 5
Default: 3°C
688
Upper limit of Zone 1 setting temperature for cooling
(at voltage level 16)
7 to 25
Default: 20°C
68C
Resolution of Zone 1 setting temperature for cooling
(Value per voltage level)
1 to 5
Default: 1°C
Hydro Unit
Terminal block (TB04) for the remote control wiring
Locally procured
2-core, non-polarity
Size : Total Length
0.5 ~ 2.5 mm
2
: Up to 50 m
AI 1 0-10V (+)
AI 2 0-10V (+)
AI 3 0-10V (+)
Common (-)
Locally procured
Size : Total Length
0.5 ~ 1.0 mm
2
: Up to 200 m
0-10V interface
PCB
CN1
CN5
1
2
3
4
DDC
(procured locally)
A B
A B
10.0
16
1
3
1.4
0.8
0.6
1.2
2
3.2
3.0
5
2.6
2.4
4
2.0
1.8
3.6
6
9
5.0
4.8
8
4.4
4.2
7
3.8
6.0
10
6.8
6.6
11
6.2
5.6
5.4
13
7.4
7.2
12
9.2
9.0
15
8.6
8.4
14
8.0
7.8
[V]
Voltage level
(Upper limit)
Analog input
Capacity direct control
• DN 680 is set to "2, 3 or 4".
DN [680]
0
1
2
3
4
AI 1
Not use
Control of Setting
tempareture
Enter settings from DN
681 to 684
Capacity direct control of
HP operation for Heating/
Cooling mode
Not use
Capacity direct control of
HP operation for Heating/
Cooling mode
AI 2
Not use
Capacity direct control of
HP operation for Hot
water mode
Capacity direct control of
HP operation for Hot
water mode
AI 3
Not use
Not use
Not use
• DN 680 = 2
Analog input enable only for Heating or cooling mode.
• DN 680 = 3
Analog input enable only for Hot water mode.
• DN 680 = 4
Analog input enable for Heating/Cooling and Hot water
mode.
10.0
10.0
110000
%
0.0
0.0
2.0
1.8
1. 4
0. 8
5.6
5.4
7755
%
5.0
4.8
7700
%
4.4
4.2
6655
%
3.8
3.6
6600
%
3.2
3.0
5555
%
2.6
2.4
5500
%
9. 2
9. 0
110000 %
8. 6
8.0
7.8
9955
%
7.4
7.2
9900
%
6.8
6.6
8855
%
6.2
6.0
8800
%
0. 8
0. 6
4.4
4.2
5555
3.8
3.6
5500
3.2
3.0
4455
2.6
%
%
%
2.0
6.6
7755
6.2
6.0
7700
5.6
5.4
6655
5.0
%
%
%
6.8
9.2
9.0
9955
8.6
8.4
9900
8.0
7.8
8855
7.4
%
1.8
1. 4
1. 2
2.4
4400
00
%
%
00
%
%
4.8
6600
7.2
8800
%
%
%
[V]
Heating / Hot water
Capacity
Demand
Analog input
No
operation
[V]
Cooling
Capacity
Demand
Analog input
No
operation
AI 1 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 2 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 1 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 2 DC0-10V (+)
35-EN
36-EN
+00_2F30151001_01EN.book 18
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
– 18 –
Hydro Unit
Installation Manual
■
0-10V interface [HWS-IFAIP01U-E] (option)
To connect the 0-10V interface
TB04 for the 0-10V interface wiring on the Hydro Unit E-BOX
• Communication wiring use 2-core non-polarity wires.
• Use 2-core shield wires to prevent noise trouble.
• In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
• Be sure not input more than DC10V to the analogue input terminals.
• The remote controller line (AB line) is available to connect maximum 2 units.
For example the header plus second remote controller or the KNX or the MODBUS or the Wireless Adapter or
the 0-10V controller.
This option allows Hydro Unit to be controlled either Setting temperatures or Capacity.
Control of Setting tempareture
• DN 680 is set to "1".
• Set the input method for each setting temperature.
• Allocate the temperature of 0 to 10V, and also set its resolution.
*( ): HWT-110
DN
Item
Selectable value (Input from)
681
Hot water setting temperature.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
682
Zone 1 setting temperature for heating.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
683
Zone 2 setting temperature for heating.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
684
Zone 1 setting temperature for cooling.
0:Not use AI
1: AI 1
2: AI 2
3: AI 3
RC : Remote controller
DN
Item
Selectable value
685
Upper limit of hot water setting temp.
(at voltage level 16)
40 to 80
Default: 65°C
689
Resolution of hot water setting temp.
(Value per voltage level)
1 to 5
Default: 5°C
686
Upper limit of Zone 1 setting temperature for heating
(at voltage level 16)
20 to 55 (65)
Default: 55°C
68A
Resolution of Zone 1 setting temperature for heating
(Value per voltage level)
1 to 5
Default: 3°C
687
Upper limit of Zone 2 setting temperature for heating
(at voltage level 16)
20 to 55 (65)
Default: 55°C
68B
Resolution of Zone 2 setting temperature for heating
(Value per voltage level)
1 to 5
Default: 3°C
688
Upper limit of Zone 1 setting temperature for cooling
(at voltage level 16)
7 to 25
Default: 20°C
68C
Resolution of Zone 1 setting temperature for cooling
(Value per voltage level)
1 to 5
Default: 1°C
Hydro Unit
Terminal block (TB04) for the remote control wiring
Locally procured
2-core, non-polarity
Size : Total Length
0.5 ~ 2.5 mm
2
: Up to 50 m
AI 1 0-10V (+)
AI 2 0-10V (+)
AI 3 0-10V (+)
Common (-)
Locally procured
Size : Total Length
0.5 ~ 1.0 mm
2
: Up to 200 m
0-10V interface
PCB
CN1
CN5
1
2
3
4
DDC
(procured locally)
A B
A B
10.0
16
1
3
1.4
0.8
0.6
1.2
2
3.2
3.0
5
2.6
2.4
4
2.0
1.8
3.6
6
9
5.0
4.8
8
4.4
4.2
7
3.8
6.0
10
6.8
6.6
11
6.2
5.6
5.4
13
7.4
7.2
12
9.2
9.0
15
8.6
8.4
14
8.0
7.8
[V]
Voltage level
(Upper limit)
Analog input
Capacity direct control
• DN 680 is set to "2, 3 or 4".
DN [680]
0
1
2
3
4
AI 1
Not use
Control of Setting
tempareture
Enter settings from DN
681 to 684
Capacity direct control of
HP operation for Heating/
Cooling mode
Not use
Capacity direct control of
HP operation for Heating/
Cooling mode
AI 2
Not use
Capacity direct control of
HP operation for Hot
water mode
Capacity direct control of
HP operation for Hot
water mode
AI 3
Not use
Not use
Not use
• DN 680 = 2
Analog input enable only for Heating or cooling mode.
• DN 680 = 3
Analog input enable only for Hot water mode.
• DN 680 = 4
Analog input enable for Heating/Cooling and Hot water
mode.
10.0
10.0
110000
%
0.0
0.0
2.0
1.8
1. 4
0. 8
5.6
5.4
7755
%
5.0
4.8
7700
%
4.4
4.2
6655
%
3.8
3.6
6600
%
3.2
3.0
5555
%
2.6
2.4
5500
%
9. 2
9. 0
110000
%
8. 6
8.0
7.8
9955
%
7.4
7.2
9900
%
6.8
6.6
8855
%
6.2
6.0
8800
%
0. 8
0. 6
4.4
4.2
5555
3.8
3.6
5500
3.2
3.0
4455
2.6
%
%
%
2.0
6.6
7755
6.2
6.0
7700
5.6
5.4
6655
5.0
%
%
%
6.8
9.2
9.0
9955
8.6
8.4
9900
8.0
7.8
8855
7.4
%
1.8
1. 4
1. 2
2.4
4400
00
%
%
00
%
%
4.8
6600
7.2
8800
%
%
%
[V]
Heating / Hot water
Capacity
Demand
Analog input
No
operation
[V]
Cooling
Capacity
Demand
Analog input
No
operation
AI 1 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 2 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 1 DC0-10V (+)
Common (-)
0-10V interface
PCB
1
2
3
4
DDC
(procured
locally)
CN5
AI 2 DC0-10V (+)
35-EN
36-EN
+00_2F30151001_01EN.book 18
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
0-10 V INTERF
ACE [HWS-IF
AIP01U-E] (OPTIONAL)
Summary of Contents for ESTIA R32 HWT-1101F21MT6W-E
Page 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Page 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Page 8: ......
Page 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Page 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Page 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Page 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Page 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Page 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Page 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Page 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Page 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Page 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Page 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Page 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Page 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Page 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...