– 14 –
Hydro Unit
Installation Manual
3-way
valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter)
can be used.
Set the 3-way valve in use with the
DN 6B4
.
NOTE
Continuous operation of the valve motor at the fully
open position is not recommended.
• The 3-way diverter valve is used to select either
domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 8, 9
and 10 on CN23.
• Connect the 3-way diverter valve in accordance with
the diagram below:
▼
Fig.7-23
▼
Fig.7-24
▼
Fig.7-25
6B4
Type 1
2-wire spring return
0
Type 2
3-wire SPST
0
Type 3
3-wire SPDT
1
8
9
10
Type 1: SPRING RETURN
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A” open
Hydro Unit
CN23
8
9
10
Type 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
8
9
10
Type 3: SPDT
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the
temperature differential needed in a 2-zone heating
system.
• Connect the 3-way mixing valve to terminals 8, 9 and
10 on CN22 (for Type 1 mixing valve) or on terminals
7, 8 and 9 on CN22 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with
the diagrams below:
▼
Fig.7-26
▼
Fig.7-27
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable
specifications” for fuse/cable size and for
connection details.
Electrical Connection (Hot Water Cylinder
Electric Heater)
• The electric heater, incorporated in the hot water
cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical
supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 02
Neutral conductor: Terminal N on Terminal Block 02
Earth Conductor: Earth terminal on Terminal Block
02
• Connect the hot water cylinder heater to the Hydro
Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on
Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2
on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal
on Terminal Block 03
▼
Fig.7-28
Electrical Connection (Hot Water Cylinder
temperature Sensor)
• Connect the hot water cylinder temperature sensor
as shown below to terminals 1 & 2 on CN20 in the
Hydro Unit.
• Please ensure that the interconnecting cable,
between the Hydro Unit and the hot water cylinder, is
connected to earth at both ends of the cable using
the shiel wire.
▼
Fig.7-29
Type 1: SPDT
8
7
9
10
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
8
7
9
10
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
1
L N
2
1
2
→
Earth leakage breaker
INPUT Power
220-240 V ~
50 Hz
Terminal block 02
Hot water
cylinder
CN20
Hydro Unit
27-EN
28-EN
+00_2F30151001_01EN.book 14
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
– 14 –
Hydro Unit
Installation Manual
3-way
valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter)
can be used.
Set the 3-way valve in use with the
DN 6B4
.
NOTE
Continuous operation of the valve motor at the fully
open position is not recommended.
• The 3-way diverter valve is used to select either
domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 8, 9
and 10 on CN23.
• Connect the 3-way diverter valve in accordance with
the diagram below:
▼
Fig.7-23
▼
Fig.7-24
▼
Fig.7-25
6B4
Type 1
2-wire spring return
0
Type 2
3-wire SPST
0
Type 3
3-wire SPDT
1
8
9
10
Type 1: SPRING RETURN
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A” open
Hydro Unit
CN23
8
9
10
Type 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
8
9
10
Type 3: SPDT
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the
temperature differential needed in a 2-zone heating
system.
• Connect the 3-way mixing valve to terminals 8, 9 and
10 on CN22 (for Type 1 mixing valve) or on terminals
7, 8 and 9 on CN22 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with
the diagrams below:
▼
Fig.7-26
▼
Fig.7-27
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable
specifications” for fuse/cable size and for
connection details.
Electrical Connection (Hot Water Cylinder
Electric Heater)
• The electric heater, incorporated in the hot water
cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical
supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 02
Neutral conductor: Terminal N on Terminal Block 02
Earth Conductor: Earth terminal on Terminal Block
02
• Connect the hot water cylinder heater to the Hydro
Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on
Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2
on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal
on Terminal Block 03
▼
Fig.7-28
Electrical Connection (Hot Water Cylinder
temperature Sensor)
• Connect the hot water cylinder temperature sensor
as shown below to terminals 1 & 2 on CN20 in the
Hydro Unit.
• Please ensure that the interconnecting cable,
between the Hydro Unit and the hot water cylinder, is
connected to earth at both ends of the cable using
the shiel wire.
▼
Fig.7-29
Type 1: SPDT
8
7
9
10
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
8
7
9
10
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
1
L N
2
1
2
→
Earth leakage breaker
INPUT Power
220-240 V ~
50 Hz
Terminal block 02
Hot water
cylinder
CN20
Hydro Unit
27-EN
28-EN
+00_2F30151001_01EN.book 14
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
– 14 –
Hydro Unit
Installation Manual
3-way
valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter)
can be used.
Set the 3-way valve in use with the
DN 6B4
.
NOTE
Continuous operation of the valve motor at the fully
open position is not recommended.
• The 3-way diverter valve is used to select either
domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 8, 9
and 10 on CN23.
• Connect the 3-way diverter valve in accordance with
the diagram below:
▼
Fig.7-23
▼
Fig.7-24
▼
Fig.7-25
6B4
Type 1
2-wire spring return
0
Type 2
3-wire SPST
0
Type 3
3-wire SPDT
1
8
9
10
Type 1: SPRING RETURN
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A” open
Hydro Unit
CN23
8
9
10
Type 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
8
9
10
Type 3: SPDT
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the
temperature differential needed in a 2-zone heating
system.
• Connect the 3-way mixing valve to terminals 8, 9 and
10 on CN22 (for Type 1 mixing valve) or on terminals
7, 8 and 9 on CN22 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with
the diagrams below:
▼
Fig.7-26
▼
Fig.7-27
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable
specifications” for fuse/cable size and for
connection details.
Electrical Connection (Hot Water Cylinder
Electric Heater)
• The electric heater, incorporated in the hot water
cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical
supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 02
Neutral conductor: Terminal N on Terminal Block 02
Earth Conductor: Earth terminal on Terminal Block
02
• Connect the hot water cylinder heater to the Hydro
Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on
Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2
on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal
on Terminal Block 03
▼
Fig.7-28
Electrical Connection (Hot Water Cylinder
temperature Sensor)
• Connect the hot water cylinder temperature sensor
as shown below to terminals 1 & 2 on CN20 in the
Hydro Unit.
• Please ensure that the interconnecting cable,
between the Hydro Unit and the hot water cylinder, is
connected to earth at both ends of the cable using
the shiel wire.
▼
Fig.7-29
Type 1: SPDT
8
7
9
10
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
8
7
9
10
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
1
L N
2
1
2
→
Earth leakage breaker
INPUT Power
220-240 V ~
50 Hz
Terminal block 02
Hot water
cylinder
CN20
Hydro Unit
27-EN
28-EN
+00_2F30151001_01EN.book 14
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
– 14 –
Hydro Unit
Installation Manual
3-way
valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter)
can be used.
Set the 3-way valve in use with the
DN 6B4
.
NOTE
Continuous operation of the valve motor at the fully
open position is not recommended.
• The 3-way diverter valve is used to select either
domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 8, 9
and 10 on CN23.
• Connect the 3-way diverter valve in accordance with
the diagram below:
▼
Fig.7-23
▼
Fig.7-24
▼
Fig.7-25
6B4
Type 1
2-wire spring return
0
Type 2
3-wire SPST
0
Type 3
3-wire SPDT
1
8
9
10
Type 1: SPRING RETURN
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A” open
Hydro Unit
CN23
8
9
10
Type 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
8
9
10
Type 3: SPDT
port “A” to Hot water
cylinder
port “AB” to
Hydro Unit
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
CN23
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the
temperature differential needed in a 2-zone heating
system.
• Connect the 3-way mixing valve to terminals 8, 9 and
10 on CN22 (for Type 1 mixing valve) or on terminals
7, 8 and 9 on CN22 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with
the diagrams below:
▼
Fig.7-26
▼
Fig.7-27
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable
specifications” for fuse/cable size and for
connection details.
Electrical Connection (Hot Water Cylinder
Electric Heater)
• The electric heater, incorporated in the hot water
cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical
supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 02
Neutral conductor: Terminal N on Terminal Block 02
Earth Conductor: Earth terminal on Terminal Block
02
• Connect the hot water cylinder heater to the Hydro
Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on
Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2
on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal
on Terminal Block 03
▼
Fig.7-28
Electrical Connection (Hot Water Cylinder
temperature Sensor)
• Connect the hot water cylinder temperature sensor
as shown below to terminals 1 & 2 on CN20 in the
Hydro Unit.
• Please ensure that the interconnecting cable,
between the Hydro Unit and the hot water cylinder, is
connected to earth at both ends of the cable using
the shiel wire.
▼
Fig.7-29
Type 1: SPDT
8
7
9
10
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
8
7
9
10
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro Unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
CN22
1
L N
2
1
2
→
Earth leakage breaker
INPUT Power
220-240 V ~
50 Hz
Terminal block 02
Hot water
cylinder
CN20
Hydro Unit
27-EN
28-EN
+00_2F30151001_01EN.book 14
ペ
?
ジ
2021
?
2
?
3
?
???
??
2
?
9
?
TOSHIBA
I 7
TOSHIBA
I 7
3-way mixing valve for 2nd zone
3-way mixing valve connection
Required controller specification:
Electrical specification: 230 V; 50 Hz; <100 mA
The 3-way mixing valve is required in order to achieve the
temperature difference in a 2-zone heating system.
• Connect the 3-way mixing valve with terminals 8, 9 and
10 at CN22 (for mixing valve type 1)
or terminals 7, 8 and 9 at CN22 (for mixing valve type 2).
• Connect the 3-way mixing valve as shown in the
following diagrams:
Electrical connection (electric heating system,
hot water cylinder)
• The electric heating system integrated
in the hot water cylinder requires a dedicated
connection to the hydro unit.
• Connect the hot water cylinder heating system
as follows:
Current-carrying: Terminal L to terminal strip 02
Neutral: Terminal N to terminal strip 02
Grounding: Grounding terminal to terminal strip 02
• Connect the hot water cylinder heating system
to the hydro unit as follows:
Current-carrying line on hot water cylinder:
Terminal 1 to terminal strip 03
Neutral line on hot water cylinder:
Terminal 2 to terminal strip 03
Grounding line on hot water cylinder:
Grounding terminal to terminal strip 03
Electrical connection (temperature sensor,
hot water cylinder)
• Connect the temperature sensor of the hot water
cylinder to terminals 1 & 2 at CN20 in the hydro
unit as shown below.
• Make sure that the connection cable between the
hydro unit and the hot water cylinder is grounded
at both ends with the shielded cable.
3-W
A
Y MIXING V
AL
VE FOR 2ND ZONE
Summary of Contents for ESTIA R32 HWT-1101F21MT6W-E
Page 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Page 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Page 8: ......
Page 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Page 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Page 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Page 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Page 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Page 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Page 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Page 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Page 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Page 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Page 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Page 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Page 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Page 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...