Function codes
Storage location
Function code no .
*HB= Hydrobox EEPROM
*RC= Remote Control
FC description
HB*
RC*
Range
Preset
Additional info
Setting the
temperature range
Upper limit temperature for zone 1 heating
1A
-
37~55°C
55
Is also the stop temperature for room temperature
control
Lower limit temperature for zone 1 heating
1B
-
20~37°C
20
Upper limit temperature for zone 2 heating
1C
-
37~55°C
55
Lower limit temperature for zone 2 heating
1D
-
20~37°C
20
Min. and max. setting range on the remote control
Upper limit temperature for cooling
18
-
20~30°C
25
Lower limit temperature for cooling
19
-
7~20°C
10
Limit to +17°C when using concrete core cooling
Upper limit temperature for domestic hot water
1E
-
60~75°C
75
Lower limit temperature for domestic hot water
1F
-
40~60°C
40
Domestic hot water
preparation
Start temperature for domestic hot water
generation
20
-
20~45°C
38
The temperature, measured at the TTW sensor, from
which domestic hot water generation is requested.
Should be set to +42°C!
Stop temperature
Domestic hot water generation
21
-
40~65°C
45
The temperature, measured at the TTW sensor, from
which domestic hot water generation is stopped.
Should be set to +60°C!
Group control - connection of the
TTW sensor:
0 = TTW sensor for connection to each Hydrobox
1 = TTW value transferred from the master unit
AB
-
0~1
0
0 = 30 minutes
1 = 60 minutes
2 = 90 minutes
3 = 120 minutes
73
-
0~3
0
Defines the time that must elapse after the heat
pump is switched on before the e-heating element
in the domestic hot water tank is activated
Domestic hot water cycle emergency heating
6AC
-
0 = Invalid
1-50h
24h
If the hot water function is not working, the hot
water is heated within the set time period
Maximum operating time
for domestic hot water
generation
Maximum operating time of the heat pump for
domestic hot water generation (min.)
07
-
1~120
30
The max. time that the HP may use for domestic hot
water generation
Attention: The backup heater in the domestic hot
water tank always switches on after 30 min., only
up to series 3
Hot water
temperature compen-
sation
Changeover temperature priority for heating/
domestic hot water generation, lower priority
22
-
-20~20°C
0
Outdoor temperature from which domestic hot water
should be generated exclusively by the backup
heater in the hot water tank
Start temperature for domestic hot water temp.
increase
24
-
-20~10°C
0
If the outdoor temperature drops below the set
value, the domestic hot water temperature is
increased by the correction factor
Correction factor for domestic hot water
temperature increase
25
-
0~15°C
3
Should be set to 0
Hot water booster
Operating time (x 10 min.)
08
-
3~18
6
The length of time for which the unit remains in
this mode after the boost button is pressed on the
remote control (e-heating element in the domestic
hot water tank active).
Domestic hot water target value
09
-
40~75°C
75
Max. temperature reached in boost mode
Anti-bacteria function
Temperature
0A
-
65~80°C
75
Temperature reached in anti-bacteria mode
Start cycle (day)
-
0D
1~10
7
Cycle after which anti-bacteria mode should be
repeated (in days)
Start time
-
0C
0~23
22
Time at which the mode is started
Cycle duration (min.)
0B
-
0~60
30
Priority mode
Switchover for external heating system
23
-
-20~20°C
-10
Bivalent switchover point to oil, gas, etc.
Priority selection:
0 = Cooling takes priority, domestic hot water is
generated by additional electric heater
1 = Domestic hot water takes priority, domestic hot
water is generated by heat pump
0F
-
0~1
0
Method by which hot water should be generated in
cooling mode
FUNCTION CODES
Summary of Contents for ESTIA R32 HWT-1101F21MT6W-E
Page 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Page 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Page 8: ......
Page 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Page 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Page 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Page 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Page 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Page 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Page 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Page 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Page 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Page 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Page 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Page 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Page 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Page 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...