8-4.
Outdoor unit
control
5) Outdoor fan control
The outdoor side control part controls the number of fan motor rotations by receiving an operation instruction from the
indoor side (Hydro unit) control part.
* Although the fan motor is a DC motor, which has non-step variable numbers of rotations, it is limited to some steps for convenience of
control.
The number of fan tap rotation allocation [rpm]
5-1) Cooling fan control
• The TL sensor, TO sensor and operation frequency control the outdoor fan. The control is performed by 1 tap of
the DC fan control (14 taps).
• For 60 seconds after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After
that, the fan is controlled according to the TL sensor temperature.
HWS-802H-E
HWS-1102H-E, 1402H-E
Item
Operation flow and applicable data, etc.
W1
W2
W3
W4
W5
W6
W7
W8
802H-E
200
230
260
300
340
380
420
460
1102,
1402H-E
Upper
200
240
240
260
320
380
480
500
Lower
200
200
200
280
360
400
500
520
W9
WA
WB
WC
WD
WE
WF
802H-E
520
570
600
630
670
710
740
1102,
1402H-E
Upper
530
610
640
660
720
780
890
Lower
550
630
660
700
740
820
910
TL [°C]
58
55
38
35
WE tap
+ 1 tap/20 secs
(Up to the maximum number of rotation for each zone)
- 1 tap/20 secs
(Up to the minimum number of rotation for each zone)
Number of rotation hold
Temperature range
Less than 20 Hz
20 Hz or more to less
than 45 Hz
45 Hz or more
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
38°C
TO
W6
WC
W8
WE
WA
WE
29°C TO < 38°C
W5
WB
W7
WD
W9
WD
15°C TO < 29°C
W4
W8
W6
WA
W8
WC
5°C TO < 15°C
W3
W6
W5
W8
W7
WA
0°C TO < 5°C
W2
W4
W4
W6
W5
W8
-4°C
TO < 0°C
W2
W3
W3
W5
W4
W6
TO < -4°C
OFF
OFF
OFF
W2
OFF
W3
TO abnormal
OFF
WC
OFF
WE
OFF
WE
Temperature range
Less than 20 Hz
20 Hz or more to less
than 45 Hz
45 Hz or more
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
38°C
TO
W6
WC
W8
WC
WA
WD
29°C TO < 38°C
W5
WB
W7
WC
(WB for 1102)
W9
WC
15°C TO < 29°C
W4
W8
W6
WA
W8
WC
5°C TO < 15°C
W3
W6
W5
W8
W7
WA
0°C TO < 5°C
W2
W4
W4
W6
W5
W8
-4°C
TO < 0°C
W2
W3
W3
W5
W4
W6
TO < -4°C
W1
W2
W1
W4
W2
W6
TO abnormal
W1
WC
W1
WC
W2
WD