47
Toshiba
8-2.
Operation
Mode and
Control Method
12) Nighttime low-noise operation
A night time low-noise operation reduces operation frequency and the number of outdoor fan rotations for a certain period
during nighttime as noise control for neighborhood.
Maximum operation frequency 40.2 Hz (Hot water supply/ Heating/ Cooling)
Maximum fan tap
460 rpm (802H-E)
500 rpm (1102H-E, 1402H-E)
The nighttime low-noise operation is enabled/ disabled by changing the remote controller FC_09.
<How to set>
1) Press the TEMP.
and TEST
button at the same time for 4 seconds or longer. (Shifted to the nighttime low-
noise setting mode)
The Code No. field displays "09", and the DATA "0000",
, and
being displayed blink.
2) Press TIME
to set enable "1" or disable "0".
Pressing SET
change DATA and
display to be lit and the setting is confirmed.
(When "1" as enable is set, the nighttime low-noise setting is enabled, the control starts at the set start time.)
3) Press TEST
to exit the nighttime low-noise time setting mode. The
and
goes out, returning to its original
status.
Item
Operation flow and applicable data, etc.
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 47 Monday, October 5, 2009 2:09 PM