Direct Access Parameter Information
https://www.toshiba.com/tic/
157
Slip Frequency Gain
Program
Motor
Vector Motor Model
This parameter provides a degree of slip compensation for a
given load. A higher setting here decreases the slip allowed for a
given load/ASD output ratio.
Direct Access Number —
F401
Parameter Type —
Numerical
Factory Default —
70
Changeable During Run —
Yes
Minimum — 0
Maximum — 150
Units — %
Autotune 2
Program
Motor
Vector Motor Model
This parameter introduces a thermal element into the autotuning
equation and is used to automatically adjust the Autotune param
-
eter values as a function of increases in the temperature of the
motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Direct Access Number —
F402
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
No
(Virtual Linear Pump) Transducer Minimum Reading
Program
Virtual Linear Pump
Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the minimum level of the transducer range
for Virtual Linear Pump operation.
Direct Access Number —
F403
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -3276.7
Maximum — 3276.7
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......