No.
7
Part name
Fan motor
(Continued)
Procedure
2. Attachment
2) Fix the fan motor lead, TC sensor and TCJ
sensor with the clamp of the bell mouth.
3) Mount the electric parts box with the fixing
screws A and B.
(Ø4 × 10, 3 pcs. Ø4 ×
10
, 1 pc.)
4) Connect the connector removed in item 1
as before and then fix wiring with the
clamp.
5) Following to work of item 2 of 2 , mount
the electric parts box cover and the suction
grille as before.
X
CAUTION
X
When exchanging the fan motors of the
models MMU-AP009 to AP030, take off
lead wire from the clamp filter, which is
connected to CN334 of the fan motor to be
exchanged and then connect the removed
lead wire to a new fan motor.
Remarks
Clamp
Fan motor lead
M6 nut
Fan motor
Motor lead
holding bracket
Fan motor
Motor lead
holding bracket
Fixing screws (Ø4 × 8)
- 88 -
Summary of Contents for Carrier MMU-AP0074HPUL
Page 15: ...2 WIRING DIAGRAM 15 ...