No.
6
Item
Air speed selection
(Continued):
Outline of specifications
Remarks
Selection of high ceiling
type CODE No. :
[5d] or selection of high
ceiling on P.C. board SW501
3) In heating operation, the mode changes to [LL] if thermostat is turned off.
1. In heating operation, the higher temperature of
TC2 sensor and TCJ sensor is compared with
temperature of TC1 sensor and then the lower
temperature is used to set the upper limit of the
fan tap.
s
When B zone has continued for 6 minutes,
the operation shifts to C zone.
s
In defrost time, the control point is set to
+6°C.
TCJ: Temperature of indoor
heat exchanger sensor
s
In D and E zones, priority
is given to remote control-
ler air speed setup.
s
In A zone “
” is displayed.
7
Prevention of cold air
discharge
E
B
A
A zone: OFF
B zone:
Over
78.8°F(
26°C
)
, below
82.4°F(
28°C
)
, ULTRA LOW (LL)
C zone:
Over
82.4°F(
28°C
)
, below
86°F(
30°C
)
, LOW (L)
D zone:
Over
86°F(
30°C
)
, below
89.6°F(
32°C
)
, MED (H)
E zone: HIGH (HH)
D
C
32
30
28
26
20
16
(°C)
CODE No.
[5d]
Standard
Type 1
Type 3
0000
0001
0003
SW501 (1)/(2)
OFF/OFF
ON/OFF
OFF/ON
Tap
COOL
HEAT
F1
HH
HH
F2
HH
HH
F3
H+
H+, H
H+, H
F4
H+
F5
HH
H
F6
HH
H
L+
L+
F7
H+
H+
L
L
F8
H
L+
F9
H
L+
L
FA
L+
L
FB
L+
L
FC
L
FD
LL
LL
LL
SVM-13085.indb 24
SVM-13085.indb 24
12/24/13 10:56 AM
12/24/13 10:56 AM
89.6
86
82.4
78.8
68
33.8
(°
F
)
COOL
HEAT
COOL
HEAT
- 21 -
Summary of Contents for Carrier MMU-AP0074HPUL
Page 15: ...2 WIRING DIAGRAM 15 ...