background image

Toshiba

– 8 –

EN

Digital Input / Output Relay Interface

Installation Manual

6

Setting

The following settings are necessary to use Digital Input / Output Relay Interfaces.
• SW1 Address set switch

When two or more Digital Input / Output Relay Interfaces are used, set a different address for each unit 
to avoid address duplication.
Assign addresses in ascending order.

CAUTION

When the SW1 setting has been changed, push the reset switch SW6. The new address setting is read.

Address of Digital Input / Output Relay Interface can be set independently from Energy Monitoring Relay 
Interface.

• SW2 Operation mode set switch
• SW3 Test switch
• SW4 Test switch

These switches are not used during normal operation. Set zero (0) or “all 
OFF”.

• SW6 Reset switch

When performing an address setting with SW1, push this reset switch after the address setting to read 
the set value.

• SW7 RS-485 terminator resistor select switch

Terminator resistor of RS-485 must be set on Energy Monitoring Relay Interface.
When Digital Input / Output Relay Interface is used without Energy Monitoring Relay Interface, set it 
[120 ohm] on Digital Input / Output Relay Interface with address SW1=1 and, set it [Open] on the other 
Interfaces.

L

BA

S

G

RS-485

 

DI

1

DI

6

DI

2

DI

4

DI

3

DI

7
DI

8

DI

5

1 2 3 4

LED1

LED2

LED3

LED4

LED5

SW1

SW2

SW3

SW4

SW6

SW7

12 V 
GND 
DO1 
DO2 
DO3 
DO4

LED6

LED7

LED8

LED9

+ -

+ -

+ -

+ -

+ -

+ -

+ -

+ -

SW1

Address set switch
1-8

Address

0, 9-F

Not used

SW2

Operating mode set switch (0 usually)

SW3

Test switch (all OFF usually)

SW4

Test switch

SW6

Reset switch

SW7

RS-485 terminator resistor select switch

120 ohm

Open

LED1

Power indicator

LED2

RS-485 communication status indicator

LED3

Not used

LED4

Test indicator

LED5

Test indicator

LED6 -LED9

Digital output indicator

ON

ON

8-EN

+00DE93229101-1_01EN.book  Page 8  Friday, October 4, 2013  2:40 PM

Summary of Contents for BMS-IFDD03UL

Page 1: ...DIGITAL INPUT OUTPUT RELAY INTERFACE Installation Manual Model name BMS IFDD03UL Toshiba 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Page 2: ...on 4 4 Installation 4 5 Connection of power cables earth wires communication cables 5 6 Setting 8 7 Test run 9 Thank you very much for purchasing this TOSHIBA Carrier Digital Input Output Relay Interface Please read this manual carefully beforehand for proper installation of the relay interface 1 EN 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Page 3: ... treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation indicated by a pic...

Page 4: ...pply 120 VAC 60 Hz Power consumption 5 W Operating temperature humidity 32 to 104 F 0 to 40 C 10 to 90 RH no condensation Storage temperature 4 to 140 F 20 to 60 C Chassis material Galvanized sheet metal 0 8 t Dimensions 2 59 H x 7 59 W x 9 68 D inch 66 H x 193 W x 246 D mm Mass 2 98 lb 1 35 kg Digital input Input type Photo coupler insulation Input points 8 points Input registance 3 k ohm Input O...

Page 5: ...xposed to rain outdoors under eaves etc Installation space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No Item Quantity Remarks 1 Digital Input Output Relay Interface 1 2 Installation Manual 1 3 Screw 4 5 32 x 0 47 M4 x 12 mm tapping screws 4 Pin...

Page 6: ... LED8 LED9 1 38 35 1 38 35 1 38 35 0 24 6 0 39 10 2 17 55 0 39 10 0 24 6 Power supply 120 VAC 60 Hz Length of stripped power cable Length of stripped communication cable Digital input contacts Smart BMS Manager Digital output load Length of stripped digital Input Output connector wire Insert the wire by pushing the lever with a screwdriver Check that the wire is inserted securely When inserting tw...

Page 7: ...sulated and left open Connection of external digital inputs Input circuit examples are shown below electrically isolated using a photo coupler CAUTION Output sink current has polarity When they are connected to inappropriate input terminal the unit may not operate properly Connection of external digital outputs Output circuit examples are shown below open collector output electrically isolated usi...

Page 8: ...ication You can set the Digital Input Output Relay Interface address independently from the Energy Monitoring Relay Interface address CAUTION The SW1 setting is read when the power is turned on Push the reset switch SW6 after changing the address Set the RS 485 terminator resistor on an Energy Monitoring Relay Interface Set SW7 as 120 ohm on a Digital Input Output Relay Interface with address SW1 ...

Page 9: ...set switch after the address setting to read the set value SW7 RS 485 terminator resistor select switch Terminator resistor of RS 485 must be set on Energy Monitoring Relay Interface When Digital Input Output Relay Interface is used without Energy Monitoring Relay Interface set it 120 ohm on Digital Input Output Relay Interface with address SW1 1 and set it Open on the other Interfaces L N B A SG ...

Page 10: ... the test switch Their output status is indicated by each LED Checking procedure 1 Set the operation mode switch SW2 to 3 in the same way as the external input check and then push the reset switch SW6 to enter the test mode 2 When the bit of the test switch SW3 is set to ON the external output turns ON when set to OFF the external output turns OFF Bits 1 to 4 of SW3 correspond to output terminals ...

Page 11: ...unication status When RS 485 communication with Smart BMS Manager is normal LED2 will blink LED Normal operation Abnormal operation LED1 Power indicator ON OFF LED2 RS 485 communication status indicator Blinking OFF LED3 Not used OFF LED4 Test indicator OFF LED5 Test indicator OFF 10 EN 00DE93229101 1_01EN book Page 10 Friday October 4 2013 2 40 PM ...

Page 12: ...DE93229101 1 Toshiba 00DE93229101 1_01EN book Page 13 Friday October 4 2013 2 40 PM ...

Reviews: