background image

 

MAINTENANCE 

 

Page 21 

 

 

 

VACUUM CHECK

 

 

A  sufficient  level  of  vacuum  is  necessary  for 

proper  performance  of  the  vacuum  interrupters. 

Although  vacuum  leaks  are  rare,  the  vacuum 

integrity  should  be  checked  periodically.    The 

relationship  between  dielectric  breakdown 

voltage of the contact gap and internal vacuum 

interrupter  pressure  has  been  found  to  be 

generally  predictable.  Therefore,  vacuum 

interrupter  integrity  is  checked  by  performing  a 

high  potential  test  across  the  open  gap  of  the 

interrupter. 

 

TEST EQUIPMENT: 

 

Toshiba offers a compact vacuum checker (Type 

CI35-1D, Figure 11) which enables a quick and 

easy  check  on  vacuum  interrupter  internal 

pressure.  Alternatively,  any  commercially 

available  AC  high  potential  tester  may  be  used 

which  is  capable  of  delivering  at  least  25  milli-

amperes at 10 kV for a period of one minute. 

 

PRECAUTIONS: 

 

Applying  abnormally  high  voltage  across  a  pair 

of contacts in vacuum may produce X-rays. The 

radiation  may  increase  with  the  increase  in 

voltage  and/or  decrease  in  contact  spacing.  X-

radiation  produced  during  this  test  with 

recommended  voltage  and  normal  contact 

spacing  is  extremely  low  and  well  below  the 

maximum  permitted  by  standards.    As  an 

additional  safety  measure,  however,  it  is 

recommended that all personnel keep at least 1 

meter  (3.3  ft)  away  from  the  vacuum  circuit 

breaker while this test is performed. 

 

Radiation exposure hazard. 

X-rays may cause illness or 

injury.  Stay at least 1 meter 

(3.3 ft) away from the circuit 

breaker during the vacuum 

check test. 

 

 

 

Hazardous voltages are 

present during dielectric 

testing which can result in 

severe injury or death.  

Only qualified personnel 

should conduct this testing. 

 

TEST PROCEDURE: 

 

1.   The  contactor  should  be  disconnected  from 

the main circuit and be in the OFF position. 

 

2.   Connect  all  the  line  side  primary  terminals 

together  and  to  the  output  of  the  vacuum 

checker  or  AC  hi-pot  machine.    Connect  all 

the load side primary terminals together and 

to  the  ground  terminal  of  the  vacuum 

checker or AC hi-pot machine. 

 

3.   Increase the voltage from zero to 10kV AC at 

a  rate  of  approximately  1kV  per  second.  

Hold  the  voltage  at  this  value  for  1  minute 

and  observe  the  current  drawn  by  the 

interrupter.  See Figure 12.

 

 

4.   Decrease the voltage back to zero.

 

 

 

Figure 11 - Toshiba Portable Vacuum 

Checker 

    WARNING

 

   WARNING

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]

Summary of Contents for 1.5kV - 600A HCV-1KAU Vacuum Contactor

Page 1: ...L INSTALLATION OPERATION MAINTENANCE HCV 1JBU Vacuum Contactor 1 5kV 600A HCV 1KAU Vacuum Contactor 1 5kV 720A Issued 12 05 Manufactured in the USA Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 3: ... Service Department Toshiba International Corporation 13131 West Little York Road Houston Texas 77041 USA or call 713 466 0277 800 231 1412 800 527 1204 Canada Fax 713 466 8773 Please complete the following information for your records and retain with this manual Model ___________________________________ Serial Number _____________________________ Date of Installation _________________________ Ins...

Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 5: ...tructions Severe property damage might also occur Means that you might be injured if you do not follow instructions Equipment damage might also occur NOTE Gives you helpful information Note The contents of this manual will not become apart of or modify the warranty policy The terms of which are set forth at the end of this manual READ SAFETY SIGNS To avoid injury you must read and follow all safet...

Page 6: ...ned and authorized to perform the service maintenance or repair of this equipment 5 Be trained in the proper care and use of protective equipment such as rubber gloves hard hat safety glasses face shield flash clothing etc in accordance with established practices 6 Be trained in rendering first aid SAFETY CODES Toshiba HCV 1JBU and HCV 1KAU vacuum contactors are designed and built in accordance wi...

Page 7: ...age Turn off and lock out Primary and Control Circuit Power before servicing Keep all panels and covers securely in place Never Defeat Modify or Bypass any Safety Interlocks Qualified Operators only DANGER Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 8: ...cuit Connections 11 Drive Unit Location 11 PRE ENERGIZATION CHECK 12 General 12 Electrical Checks 12 OPERATION 13 Moving Contactor from Disconnected to Connected Position 13 Moving Contactor from Connected to Disconnected Position 13 Internal Connection of the Normally Energized Type 14 Configuration of the Drive Unit 14 Standard Operation Circuit of the Normally Energized Type 15 MAINTENANCE 16 M...

Page 9: ...ce Life 23 Mechanical Service Life 23 Wipe Measurement 23 Service Life of Capacitor 23 Table 4 Recommended Part Replacement Intervals 23 Capacitor Switching Life 23 STORAGE AND DISPOSAL 24 Storage 24 Inspection during Storage 24 Disposal SPECIFICATIONS 25 Table 5 Ratings 25 WARRANTY AND LIMITATION OF LIABILITY 26 Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomatio...

Page 10: ...r their English equivalent This manual is divided into major sections of interest as follows GENERAL DESCRIPTION Provides a description of the equipment information on major components and how they function plus rating information RECEIVING INSPECTION AND HANDLING Describes procedures for receiving unpacking inspecting handling lifting and moving the contactors INSTALLATION Provides information on...

Page 11: ...surge contact materials which exhibit low current chopping levels reducing switching overvoltage Front view Figure 1 1 Insulation frame 2 Vacuum Interrupter 3 Primary terminal 4 Flexible conductor Side view Figure 2 1 Drive unit 2 Auxiliary switch 3 Shaft Rear view Figure 3 1 Closing coil 2 Opening spring 3 Terminal block Figure 1 Front of Contactor Figure 2 Right Side of Contactor Figure 3 Rear o...

Page 12: ...ndicates if the contactor is OFF Green or ON Red When the indicator reads OFF the main contacts of the contactor are open When the indication is ON the main contacts are closed See Figure 4 Figure 4 ON OFF Indicator Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 13: ...led damage 3 Check for the presence of accessories that are shipped with the contactor Contactor wear gauge Figure 5 4 Keep the contactor upright Never lay the contactor on its side or upside down This may cause damage File a claim with the carrier for any damaged or missing items and immediately notify the nearest Toshiba representative Do not install or energize equipment that has been damaged D...

Page 14: ...esigned to mount to a flat vertical surface If there are any noticeable gaps between the contactor and the mounting surface fill them in using flat washers as spacers Fasten the contactor using four 4 M8 hex head bolts The tightening torque should be 120 150 kgf cm 9 11 ft lb See Table 1 for tightening torque specifications MAIN CIRCUIT CABLE CONNECTIONS Route cables that connect to the contactor ...

Page 15: ...ontactor and crimp the terminal to the end of the ground wire Figure 6 Ground Connection Location The ground wire should be 8 AWG or larger Then reattach the terminal using the same bolt previously removed and torque to 9 11 ft lb 120 150 kgf cm CONTROL CIRCUIT CONNECTIONS Hazardous Voltage Turn off and lock out all primary and control circuit power sources prior to performing this pre energizatio...

Page 16: ...s and covers if removed Check for any loose connections and confirm that all wiring is correct per wiring diagrams A supply of spare parts should be established Instruction manuals and diagrams should be collected and filed ELECTRICAL CHECKS Electrical shock hazard Do not touch energized components during a test using auxiliary power An electrical insulation resistance test should be performed to ...

Page 17: ...ON position 2 Verify that the position indicator reads ON Red MOVING THE CONTACTOR FROM THE ON TO THE OFF POSITION TO MOVE THE CONTACTOR TO THE OFF POSITION 1 Turn OFF circuit control power to move the contactor to the OFF position 2 Verify that the position indicator reads OFF Green Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 18: ...LEGEND 52 CC Closing Coil T1 T4 Terminal Block A1 A2 Closing Supply AC DC LEGEND 52 CC Closing Coil T1 T2 Terminal Block A1 A2 Closing Supply AC DC 16 15 14 13 12 11 26 25 24 23 22 21 52 CC 52 CC Auxiliary Switch Drive Unit A1 A2 Closing Supply AC DC T4 T3 T2 T1 U V W R S T Vacuum Bottles 1 2 5 6 Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 19: ...t e ON OFF OFF A2 A1 CR 16 15 14 13 12 11 26 25 24 23 22 21 VCTT GL 52 CC 52 CC T2 T1 2E Over l oad ON 1 0 0 1 1 0 V 2 0 0 2 2 0 V A C D C Auxili ary Swi tch Dri ve Uni t CR CR RL LEGEND 52 CC Closing Coil T1 T2 Terminal Block GL Green Light RL Red Light CR Control Relay A1 A2 Closing Supply AC DC Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...

Page 20: ...nated insulators can allow a short circuit or ground fault to occur NOTE Refer to the SAFETY section of this manual for important information MAINTENANCE RECORD Keep a permanent record of all maintenance work At a minimum this record should include information on 1 Items inspected 2 Reports of any testing 3 Equipment condition 4 Corrective actions or adjustments 5 Date of work 6 Comments The degre...

Page 21: ...ths 3 Periodic Inspection Inspection is performed with the contactor de energized The lubrication of sliding and rotating parts is checked and the mechanism is lubricated if needed Inspection Frequency Once every 1 2 years or every 20 000 operations normal NOTE Refer to Table 2 for the schedule of Periodic Inspections 4 Unscheduled Inspection Inspections are implemented as required Inspection Freq...

Page 22: ...ion or damage Wipe with clean dry cloth Lubricate if necessary Smooth operation Visual inspection or touch Check lubrication Make sure moving parts operate smoothly Apply a small amount of lubrication Main Circuit Terminals and movable conductors Visual inspection Tighten using screwdriver or wrench Make sure there is no discoloration or loose fasteners Check the cause and repair Tighten connectio...

Page 23: ...eating and discoloration Replace if damaged Wiring Visual inspection Tighten using a screwdriver Check for discoloration and tightness Repair if disconnected Tighten if loose See Table 1 for tightening torque specifications Insulation Resistance Measure ment Resistance from main circuit to ground Measure insulation resistance between phases between electrodes and between circuits and ground Megger...

Page 24: ... confirm the correct operation If not normal check and repair If necessary replace faulty parts Table 3 Gap Wipe Standard Values contactor in new condition Parts Gap Wipe Allowable Wear Vacuum Interrupter Normally energized type 0 091 0 098 in 2 3 2 5 mm 0 091 0 102 in 2 3 2 6 mm 0 051 in 1 3 mm a contact 0 157 0 016 in 4 0 4 mm 0 118 0 012 in 3 0 3 mm b contact 0 157 0 016 in 4 0 4 mm 0 118 0 012...

Page 25: ...al contact spacing is extremely low and well below the maximum permitted by standards As an additional safety measure however it is recommended that all personnel keep at least 1 meter 3 3 ft away from the vacuum circuit breaker while this test is performed Radiation exposure hazard X rays may cause illness or injury Stay at least 1 meter 3 3 ft away from the circuit breaker during the vacuum chec...

Page 26: ... vacuum level After the test is complete discharge any residual static charge from the primary terminals of the circuit breaker If a vacuum checker or AC hi pot tester is not available a DC hi potential test may be conducted If a DC test is conducted the test voltage must be increased to 14kV DC The test duration for DC tests and the criteria for acceptance remain the same as for AC tests Do not u...

Page 27: ...ations For the components listed in Table 4 replacement or detailed inspection and cleaning are recommended after the indicated number of operations Figure 13 Wipe Measurement Table 4 Recommended Part Replacement Intervals Part Name Number of Operations for Replacement Vacuum Interrupter 500 000 Auxiliary Switch 200 000 Moveable Core Detailed inspection and cleaning every 500 000 operations Statio...

Page 28: ...on is necessary if storage is for an extended period The unit should be checked for condensation moisture corrosion and vermin Prior to installation the contactor should be carefully examined for evidence of physical damage corrosion or other deterioration Refer to the PRE ENERGIZATION Section of this manual The MAINTENANCE section of this manual describes various types of inspections recommended ...

Page 29: ...t kA 4 8 close open 25 times 5 76 close open 25 times Rated Insulation Level kV AC 10 Impulse 45 AC 10 Impulse 30 Rated Short Time Current kA 9 0 1 sec 3 6 30 sec 10 8 1 sec 4 3 30 sec Method of Operation Non latch Mechanical Operation Million 2 5 Electrical Operation Million 0 5 Operational Voltage Standard 100 240V AC DC Auxiliary Switch 3 N O 3 N C Switching Frequency Times h 1200 Phone 800 894...

Page 30: ...USERS OF THE EQUIPMENT AND PARTS FOR BREACH OF THE FOREGOING WARRANTY THE COMPANY WILL HAVE NO OBLIGATIONS TO DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COSTS INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION THE COMPANY TOSHIBA CORPORATION AND THEIR SUPPLIERS A...

Reviews: