Overspeed
You need to be logged in to do this test. Press Config button (On the membrane). Go to Config>Advanced>Engine
Speed. Start your engine. Press Overspeed Test button.
Electronic Control Module Selector Switch in Alternate Position (301)
Disconnect #301 engine wire. Put a jumper between #301 input and ground (See drawing for more details).
Fuel Injection Malfunction (302)
Disconnect #302 engine wire. Put a jumper between #302 input and ground (See drawing for more details).
Electronic Control Module Warning ( 303 )
Disconnect #303 engine wire. Put a jumper between #303 input and ground (See drawing for more details).
Electronic Control Module Fault ( 304 )
Disconnect #304 engine wire. Put a jumper between #304 input and ground (See drawing for more details).
Low Engine Temperature (312)
Disconnect #312 engine wire. Put a jumper between #312 input and ground (See drawing for more details).
Low Oil Pressure
Disconnect Oil Pressure connector. Depending of your sensor type, put a jumper between positive pin (left) or
negative pin (right) and signal pin (middle) of this connector (See drawing for more details).
High Engine Temperature
Disconnect Engine Temperature connector. Depending of your sensor type, put a jumper between positive pin (left)
or negative pin (right) and signal pin (middle) of this connector (See drawing for more details).
Battery 1 Failure
Disconnect #6 engine wire (See drawing for more details).
Battery 2 Failure
Disconnect #8 engine wire (See drawing for more details).
Weak Battery 1
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Weak Battery 1 setpoint to maximum allowable.
Weak Battery 2
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Weak Battery 2 setpoint to maximum allowable.
Battery 1 Overvoltage
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Overvoltage Battery 1 setpoint to minimum allowable.
Battery 2 Overvoltage
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Overvoltage Battery 2 setpoint to minimum allowable.
Loss of Continuity 1
Disconnect #9 engine wire (See drawing for more details). Wait 1-2 minutes.
Loss of Continuity 2
Disconnect #10 engine wire (See drawing for more details). Wait 1-2 minutes
Low Pneumatic Pressure
Put a jumper between the Low Pneumatic Pressure input and ground (See drawing for more details). Take note that
this alarm will stop the pneumatic cranking sequence.