TOPVERT G1/H1/P1 Series
E-28
Pr5-23
Over-Torque Detection Time 2 (ot2)
0.0
~
60.0 Sec
0.1
Pr5-24
{Pr5-21}
Most Recent Fault Record
0: no fault
0
Pr5-25
{Pr5-22}
2nd Most Recent Fault Record
1: oC (over-current)
Pr5-26
{Pr5-23}
3rd Most Recent Fault Record
2: oU (over-voltage)
Pr5-27
{Pr5-24}
4th Most Recent Fault Record
3: GF (ground fault)
◎
Pr5-28
5th Most Recent Fault Record
4: SC (IGBT failure)
◎
Pr5-29
6th Most Recent Fault Record
5: oL (drive overload)
◎
Pr5-30
7th Most Recent Fault Record
6: oL1 (electronic thermal relay 1)
◎
Pr5-31
8th Most Recent Fault Record
7: ot1 (Over-Torque1)
◎
Pr5-32
9th Most Recent Fault Record
8: oCn
(over-current during constant speed)
◎
Pr5-33
10th Most Recent Fault Record
9: oCA (over-current during accel.)
◎
Pr5-34
11th Most Recent Fault Record
10: oCd (over-current during decel.)
◎
Pr5-35
12th Most Recent Fault Record
11: EP1 (EPROM error 1)
◎
Pr5-36
13th Most Recent Fault Record
12: EP2 (EPROM error 2)
◎
Pr5-37
14th Most Recent Fault Record
13: EF (external fault)
◎
Pr5-38
15th Most Recent Fault Record
14: Ct1 (current sensor 1)
◎
Pr5-39
16th Most Recent Fault Record
15: Ct2 (current sensor 2)
16: HPF (protection circuit fault)
17: oH1 (IGBT overheat)
18: oH2 (Heatsink overheat)
19: SoFt (Pre-charge circuit error)
20: ACI. (AI2 error)
21: ASC (RS-485 error)
22: PI.d (PID error)
23: Pu(Keypad communication overtime)
24: tunE (Auto tuning failure)
25: bF (braking chopper failure)
26: PG (PG error)
27: PHL
(Phase-Loss protect or capacitor aged)
28: CC (current signal error during stop)
29: CPu (CPU error)
30: FAn (Fan failure)
31: AnI fault (Analog input error)
32: ot2 (Over-Torque2)
◎
33: oL2 (electronic thermal relay 2)
◎
34: rnot (Motor selection error)
◎
36: LUr (Low Voltage during Run)
◎
37: oUd (over-voltage during decel)
38: `x CoPY (Parameter copy error)
◎
39: LU (Low Voltage)
40: bb (External Base Block )
★
◎
Pr5-40
Full-Load Current of Motor 2
Amp (10~120% of drive’s rated current)
##.##
◎
Pr5-41
Auto Torque Compensation of Motor 2
0.0
~
25.0%
0.0
◎
Pr5-42
Slip Compensation of Motor 2
0
~
20 RPM
0
◎
Pr5-43
Number of Motor Poles 2
2
~
20
4
◎
Pr5-44
Rotor Resistance R1 of Motor 2
0.000
~
65.535
Ω
0
◎
Pr5-45
Motor 2- Electronic Thermal Relay
Selection (oL2)
0: Electronic thermal relay function
disabled
0
1: Inverter duty motor
(with independent cooling fan)
2: Standard motor
(with shaft mounted cooling fan)