TOPVERT G1/H1/P1 Series
E-27
★
Pr5-07
Over-Voltage Stall Prevention Level
230V models: 320
~
500VDC
380
460V models: 640
~
1000VDC
760
◎
575V models: 800
~
1250VDC
950
Pr5-08
Software Braking Level
230V models: 320
~
500VDC
373
460V models: 640
~
1000VDC
746
◎
575V models: 800
~
1250VDC
932
Pr5-09
Phase-Loss Protection
0: Warn and keep operation (below 50%)
0
1: Warn and ramp to stop
2: Warn and coast to stop
Pr5-10
Over- Current Stall Prevention level
during accel on the constant torque
region
Amp (10~250% of drive’s rated current)
##.##
Pr5-11
Over- Current Stall Prevention low-limit
level during accel on the constant
power region
Amp (0~250% of drive’s rated current)
##.##
Pr5-12
Over-Current Stall Prevention level
during constantant speed on the
constant torque region Operation
Amp (10~250% of drive’s rated current)
##.##
Pr5-13
Over- Current Stall Prevention low-limit
level during constant speed run on the
constant power region
Amp (0~250% of drive’s rated current)
##.##
Pr5-14
Over-Current Deceleration Time during
Operation
0.050~600.00 Sec
3.00
Pr5-15
Over-Torque Detection Selection 1
(ot1)
0
:
Disabled
0
1
:
Over-torque detection during constant
speed operation, stop operation after
detection.
2
:
Over-torque detection during constant
speed operation, continue to operate
after detection.
3
:
Over-torque detection during operation,
stop operation after detection
4
:
Over-torque detection during operation,
continue operation after detection.
Pr5-16
Over-Torque Detection Level 1 (ot1)
Amp(10
~
250% of drive’s rated current)
##.##
Pr5-17
Over-Torque Detection Time 1 (ot1)
0.0
~
60.0 Sec
0.1
Pr 5-18
Motor 1- Electronic Thermal Relay
Selection (oL1)
0
:
Electronic thermal relay function
disabled
0
1
:
Inverter duty motor
(with independent cooling fan)
2
:
Standard motor
(with shaft mounted cooling fan)
Pr5-19
Motor 1- Electronic Thermal Relay
Characteristic
30
~
600 Sec
60
Pr5-20
IGBT Over-Heat pre–warning setting
(oH2)
0.0~110.0
85.0
Pr5-21
Over-Torque Detection Selection 2
(ot2)
0: Disabled
0
1: Over-torque detection during constant
speed operation, stop operation after
detection.
2: Over-torque detection during constant
speed operation, continue to operate
after detection.
3: Over-torque detection during entire
(acceleration, steady state,deceleration)
operation, stop operation after detection
4: Over-torque detection during entire
(acceleration, steady state,deceleration)
operation, continue operation after
detection.
Pr5-22
Over-Torque Detection Level 2 (ot2)
Amp(10
~
250% of drive’s rated current)
##.##