Take Notice:
if it is selected a different system type from the previous one programmed, it will start an Internal
Cleaning.
WARNING!:
Before selecting the system type ensure that the two quick fittings of high and low pressure located at
the end of the hoses are connected to the two male connectors on the station (img 6-g)
DO NOT EVER RUN AN INTERNAL CLEANING WITH THE FITTINGS CONNECTED TO THE VEHICLE
WAIT
until the end of the internal cleaning to proceed. The cleaning operation will end when the display shows a
message, after the oil drain.
WARNING!
If the internal cleaning is interrupted it will be requie every time, even selecting the same system type.
Use the arrow “right/left” keys to navigate through the different functions.Use the arrows “up/down” to set up the
functions
as described on paragraph 10.3.1 “Operation description menu Manual/Automatic”.
Take Notice:
it is possible to set up the oil automatically as follows:
1) setting up the desider quantity;
2) Charging the same amount of oil drained after the Recovery function. To set up this option select “A” by
using the “down” arrow key (under the 0 value it will be visualized “A”).
After changing the parameters, navigate with the arrow keys until the “START” symbol on the left, open “High
pressure” and “Low pressure” taps, then press “Enter” to confirm.
It will run automatically the whole cycle.
For the recovery phase, the automatic cycle provides 2 recoveries with a 2 minutes pause in stand-by mode.
Once the cycle is finished the display will show a “Automatic Cycled finished Press ENTER” message.
The current gas inside the RR2200 hoses can be recovered by removing the quick fittings from the AC system and
selecting the Recovery (see paragraph 10.3.1 manual recovery function).
At the end of the cycle it will be possible to print the operation by pressing the “Print” key (only Printer version).
The display will show a “Individual printing” message. Press “Enter” to start the operation.
Take notice:
do not pull the paper while printing.
If leakage is detected, the display will show a "leak system" message
(only if the leaking test was previously
programmed), in that case it will be necessary to find the leakage with thehelp of a leak detector lamp or a leak
detector (accessories upon request).
Take notice:
if a function standard is positioned on
zero that function will not be executed.
Take notice
: If the current amount of gas in the internal bottle before starting the stage is less than 1
K
g, the
display will show a “insufficient gas” message. Run an internal bottle recharge.
Image 25
– Standard
Image 26
– Hybrid