TOELLNER TOE 9261 Instruction Manual Download Page 14

 

Section 2 

– Operation 

 

 

TOELLNER Electronic Instrumente GmbH 

14 

2.6 

Protection 

Series 

TOE 9261

 devices use various protective devices which serve to prevent serious 

damage to the units. 

 

Warning

 

Make absolutely sure that the supplying voltage source is connected to the input sockets 

Plus 

– Minus

 with the proper polarity! 

 
Feedback from the (buffered) load side to the 

OUT

 output of the power switch must have 

the indicated polarity and not exceed the rated voltage of the 

TOE 9261

, i.e. the voltage 

connected to 

OUT

 must not be more positive than the voltage at the 

Plus

 sockets or more 

negative than the voltage at the 

Minus

 sockets! A voltage exceedance into the negative or 

positive direction is only permissible after blocking 

S1

 or 

S2

 by means of inductance-

dependent, further flowing load current 
 

Non-observance of these instructions may result in damage to the Electronic 
Switch. 

 

 

2.6.1 

Overcurrent and short-circuit protection of the switching paths 

The overcurrent and short-circuit protection of the switching paths is designed to guard the 

TOE 9261

 against overload from excessive currents. It extends through the longitudinal and 

branch paths of the power switch as well as through the signal line switches. 

When the overcurrent and short-circuit protection is triggered, the internal driver stages are 
permanently turned off, i.e. the switching paths are no longer driven. 

This fault status is indicated by the 

OVL

 LED. 

A reset is accomplished by turning the unit off and on using the mains switch. The cause of 
the overcurrent or short-circuit must be identified and eliminated. 

 

2.6.2 

Input overcurrent protection 

The input overcurrent protection guards the power switch against excessively high periodic 
supply of power which results from the inductance on the input cable at the moment the 
longitudinal path is turned off. 

When the input overcurrent protection is triggered, the internal driver stages are permanently 
turned off, i.e. the switching paths are no longer driven.   

A fault condition is indicated by the 

OVL

 LED. 

Reset by turning the unit off and on using the mains switch. 

The following measures can be taken to prevent too high periodic supply of inductive energy 
and thereby an undesired triggering of the input overcurrent protection: 

 

Minimize the cable length to the input sockets 

Plus 

– Minus

 

 

Parallel, closely adjacent routing of both cable conductors 

 

Use of a feed source with high output buffer capacity 

 

Apply the built-in input buffer capacitor 

 

2.6.3 

Protection against exceeding of the maximum switching frequency 

To protect against excessive switching losses and against excessive driver output, the 
maximum switching frequency is limited. 

Applying a higher frequency at the 

CONTROL

 input results in shutting off of the internal 

driver stages, i.e. the switching paths are no longer driven. 

This fault condition is indicated by the 

OVL

 LED. 

The fault condition remains as long as the non-permitted switching frequency is present. If 
the frequency is first reduced significantly below the permissible limit (taking into account a 

Summary of Contents for TOE 9261

Page 1: ...n Manual Electronic Switch TOE 9261 9261E Manual Rev05 doc R TOELLNER ELECTRONIC INSTRUMENTE GMBH Gahlenfeldstra e 31 58313 Herdecke Germany 49 0 23 30 97 91 91 Fax 49 0 23 30 97 91 97 E Mail info toe...

Page 2: ...switching a ground line minus 10 2 4 6 Connection of the control signal 10 2 4 7 Control of switching paths and operation of the consumer 10 2 4 8 Display of the switching states 11 2 4 9 Use of the b...

Page 3: ...ual When operating electronic equipment certain parts in these devices are necessarily under dangerous voltage Non observance of the warnings may therefore result in severe bodily injury or damage to...

Page 4: ...a feeding source to the connected consumer The branch path in this case is arranged parallel to the consumer and can be optionally connected via a DIL switch It serves as needed to selectively dischar...

Page 5: ...h TTL CMOS 5 V and LVCMOS 3 3 V Permissible switching frequency DC up to 100 kHz Protected against overcurrent short circuit excessive temperature excessive switching frequency 1 2 Model overview Seri...

Page 6: ...result in a hazardous condition for the device No intentional interruption of the protective earth connection is permitted Observe local regulations for earthing Ensure that only fuses of the specifi...

Page 7: ...or rear CONTROL input 3 Front panel BNC input CONTROL for controlling the switching state both for the power switch and the signal line switches 2 4 7 Control of switching paths and operation of the c...

Page 8: ...e illuminated 12 Red OVL LED Overload Comes on when a shutdown has occurred due to one of the following fault conditions Max switching frequency of 100 kHz on the control input has been exceeded Overc...

Page 9: ...f the consumer for switching a ground line the input voltage should be connected to this socket and to the Minus socket otherwise to the left hand Plus socket and the Minus socket The applied voltage...

Page 10: ...also the above mentioned improper load current flow via the 0 1 resistor is automatically locked Warning In the described switch configuration the positive supply line from the voltage source to the c...

Page 11: ...PULL UP ON to ON the internally evaluated level changes to High resulting in switching path S1 becoming conductive and switching path S2 non conductive In the configuration for switching the positive...

Page 12: ...e rise and fall times are lengthened High buffer capacities with low series resistance values ESR can also result in triggering of the overcurrent fuse Warning Feedback from the buffered load side to...

Page 13: ...ged by excessive ripple current loads 2 5 Operation of the signal line switches 2 5 1 Connection To switch signal lines they are routed through the bidirectional switches S3 S6 They are connected usin...

Page 14: ...reset is accomplished by turning the unit off and on using the mains switch The cause of the overcurrent or short circuit must be identified and eliminated 2 6 2 Input overcurrent protection The input...

Page 15: ...n responds to excessive component temperatures in the unit This protection is provided in two stages For continuous operation at high voltage high current and high switching frequency the fan speed is...

Page 16: ...to the 19 adapter piece 1 Insert this unit in replacement for the fill strip and screw it on to the front panel using the hexagon socket screws 6 4 For the other side attach the adapter bracket 3 to...

Page 17: ...ice Pull the four fill strips 5 from the side 3 For the outer faces of the devices attach a handle 4 to a 19 adapter piece 1 each using the countersunk screws 7 Insert these units in replacement for t...

Page 18: ...ower switch switching times Rise time tr with reference resistor 1 With connected input buffer capacitor Without buffer capacitor input cable 0 50 m twisted Without buffer capacitor input cable 1 20 m...

Page 19: ...Increase in fan speed Stage 2 Switching off of switching paths display OVL Switching off and on again using mains switch following appropriate cooling period Power switch is not reverse polarity prot...

Page 20: ...luded accessories 1 mains cable 2 terminal blocks for signal line switches 1 Instruction Manual Optional accessories 0 50 m connection cable with 1 safety socket red TOE 9260 22 0 50 m connection cabl...

Page 21: ...t 8 Selectable base load 10 k or 100 k with green indication LED 9 Power switch branch path incl red indication LED 10 0 series resistor for branch path with green indication LED 11 0 1 series resisto...

Reviews: