TOELLNER TOE 9261 Instruction Manual Download Page 10

 

Section 2 

– Operation 

 

 

TOELLNER Electronic Instrumente GmbH 

10 

2.4.4 

Connection of the consumer for switching the positive supply line 

The consumer to be operated is connected to the 

OUT

 socket and the right-hand 

Minus

 

socket. Since the 

S1

 switch carries the load current, the DIL switch 

 S1 ENABLE  

 must be in 

the left position. 

Warning

 

In the described switch configuration, the negative return line must always be connected 
from the consumer to the voltage source via the minus sockets of the 

TOE 9261

. These 

minus sockets must never be bypassed, because otherwise some protection mechanisms 
of the Electronic Switch are without effect, and damage to the Electronic Switch may 
result. 

 

2.4.5 

Connection of the consumer for switching a ground line (minus) 

The consumer to be operated is connected with the positive pole to the right-hand 

Plus

 

socket and the negative pole to the 

OUT

 socket. The latter is the switched ground point. 

Since the load current is connected via the 

S2

 switch in this configuration, this must be 

activated using the DIL switch 

 S2 + 0 

Ω 

 in position 

 ON 

. The green LED next to the related 

switch symbol is illuminated. 

Warning

 

When switching a ground line (minus), the 

 S2 + 0.1 

Ω 

 setting must never be selected, 

otherwise the internal 0.1 

Ω resistor would be overloaded during the flow of current. 

 

The 

S1

 switch parallel to the load can be deactivated by setting the DIL switch 

 S1 ENABLE 

 to 

 OFF 

. Otherwise the load would be discharged via 

S1 

during the interruption. With 

deactivation of the 

S1

 switch also the above-mentioned improper load current flow via the 

0.1 

Ω resistor is automatically locked. 

Warning

 

In the described switch configuration, the positive supply line from the voltage source to 
the consumer must always be connected via the 

Plus

 sockets of the 

TOE 9261

. These 

plus sockets must never be bypassed, because otherwise some protection mechanisms of 
the Electronic Switch are without effect, and damage to the Electronic Switch may result. 

 

2.4.6 

Connection of the control signal 

A digital switching signal for controlling the power switch can be connected

 

as desired to the 

front panel or rear BNC 

CONTROL

 socket. A suitable clock source must be provided. This 

signal should be compatible with one of the logic standards CMOS 5 V, LVCMOS 3.3 V or 
TTL. Suitable devices include function generators in square wave or pulse mode as well as 
arbitrary waveform generators (AWG) with digital waveforms. Voltages above 5 V as well as 
negative voltages or voltages which extend into the negative range may not be used. Control 
signals with a frequency up to 100 kHz can be used. An overload switch-off is carried out 
above this frequency. 

 

2.4.7 

Control of switching paths and operation of the consumer 

The digital switching signal is used to control the state of the paths 

S1

 and 

S2

. A conductive 

path is thereby indicated by the red LED at the switch symbol 

S1

 or 

S2

 (

 2.4.8 Display of 

the switching states). If the DIL switch 

 CONTROL / INV 

 is in the left position (i.e. no inversion), 

S1

 is conductive and 

S2

 is non-conductive during a High level of the switching signal. 

If however the DIL switch 

 CONTROL / INV 

 is set to 

 INV 

S1

 is non-conductive and 

S2

 is 

conductive during a High level of the switching signal. 

 

Summary of Contents for TOE 9261

Page 1: ...n Manual Electronic Switch TOE 9261 9261E Manual Rev05 doc R TOELLNER ELECTRONIC INSTRUMENTE GMBH Gahlenfeldstra e 31 58313 Herdecke Germany 49 0 23 30 97 91 91 Fax 49 0 23 30 97 91 97 E Mail info toe...

Page 2: ...switching a ground line minus 10 2 4 6 Connection of the control signal 10 2 4 7 Control of switching paths and operation of the consumer 10 2 4 8 Display of the switching states 11 2 4 9 Use of the b...

Page 3: ...ual When operating electronic equipment certain parts in these devices are necessarily under dangerous voltage Non observance of the warnings may therefore result in severe bodily injury or damage to...

Page 4: ...a feeding source to the connected consumer The branch path in this case is arranged parallel to the consumer and can be optionally connected via a DIL switch It serves as needed to selectively dischar...

Page 5: ...h TTL CMOS 5 V and LVCMOS 3 3 V Permissible switching frequency DC up to 100 kHz Protected against overcurrent short circuit excessive temperature excessive switching frequency 1 2 Model overview Seri...

Page 6: ...result in a hazardous condition for the device No intentional interruption of the protective earth connection is permitted Observe local regulations for earthing Ensure that only fuses of the specifi...

Page 7: ...or rear CONTROL input 3 Front panel BNC input CONTROL for controlling the switching state both for the power switch and the signal line switches 2 4 7 Control of switching paths and operation of the c...

Page 8: ...e illuminated 12 Red OVL LED Overload Comes on when a shutdown has occurred due to one of the following fault conditions Max switching frequency of 100 kHz on the control input has been exceeded Overc...

Page 9: ...f the consumer for switching a ground line the input voltage should be connected to this socket and to the Minus socket otherwise to the left hand Plus socket and the Minus socket The applied voltage...

Page 10: ...also the above mentioned improper load current flow via the 0 1 resistor is automatically locked Warning In the described switch configuration the positive supply line from the voltage source to the c...

Page 11: ...PULL UP ON to ON the internally evaluated level changes to High resulting in switching path S1 becoming conductive and switching path S2 non conductive In the configuration for switching the positive...

Page 12: ...e rise and fall times are lengthened High buffer capacities with low series resistance values ESR can also result in triggering of the overcurrent fuse Warning Feedback from the buffered load side to...

Page 13: ...ged by excessive ripple current loads 2 5 Operation of the signal line switches 2 5 1 Connection To switch signal lines they are routed through the bidirectional switches S3 S6 They are connected usin...

Page 14: ...reset is accomplished by turning the unit off and on using the mains switch The cause of the overcurrent or short circuit must be identified and eliminated 2 6 2 Input overcurrent protection The input...

Page 15: ...n responds to excessive component temperatures in the unit This protection is provided in two stages For continuous operation at high voltage high current and high switching frequency the fan speed is...

Page 16: ...to the 19 adapter piece 1 Insert this unit in replacement for the fill strip and screw it on to the front panel using the hexagon socket screws 6 4 For the other side attach the adapter bracket 3 to...

Page 17: ...ice Pull the four fill strips 5 from the side 3 For the outer faces of the devices attach a handle 4 to a 19 adapter piece 1 each using the countersunk screws 7 Insert these units in replacement for t...

Page 18: ...ower switch switching times Rise time tr with reference resistor 1 With connected input buffer capacitor Without buffer capacitor input cable 0 50 m twisted Without buffer capacitor input cable 1 20 m...

Page 19: ...Increase in fan speed Stage 2 Switching off of switching paths display OVL Switching off and on again using mains switch following appropriate cooling period Power switch is not reverse polarity prot...

Page 20: ...luded accessories 1 mains cable 2 terminal blocks for signal line switches 1 Instruction Manual Optional accessories 0 50 m connection cable with 1 safety socket red TOE 9260 22 0 50 m connection cabl...

Page 21: ...t 8 Selectable base load 10 k or 100 k with green indication LED 9 Power switch branch path incl red indication LED 10 0 series resistor for branch path with green indication LED 11 0 1 series resisto...

Reviews: