background image

IP-EN1-EB  Instruction Manual 

4.3  Emergency Control Input CN13 and System Settings 

A single control input with two poles is provided that can be used for activating emergency, 
and  resetting  emergency  or  activating  silence.  When  activating  silence,  then  emergency 
reset must be controlled by an emergency or fireman microphone, or a separate contact 
connected directly to the VA system. The corresponding settings in the setting software are 
described  in  the  chapter  5.2  for  the  VX-2000  system  and  in  the  chapter  6.3  of  the  
SX-2000 system. 

There are various combinations to connect the emergency controls from the FDS, please 
find the settings in the indicated chapter: 

VX-2000 

Emergency activation 

Emergency 

reset 

Silence 

chapter 

by contact 

by voltage 

make 

break  

on 

off 

 

 

 

 

  

 

  4.3.3 * 

 

 

 

 

 

 

4.3.4 

 

 

 

 

 

 

4.3.5 

 

 

 

 

 

 

4.3.6 

 

 

 

 

 

 

4.3.7 

 

 

 

 

 

 

4.3.8 

 

 

 

 

 

 

4.3.9 

 

 

 

 

 

 

4.3.10 

* : factory preset 

SX-2000 

Emergency activation 

Emergency 

reset 

Silence 

chapter 

by contact 

by voltage 

make 

break  

on 

off 

 

 

 

 

 

 

  4.3.3 * 

 

 

 

 

 

 

4.3.5 

 

 

 

 

 

 

4.3.7 

 

 

 

 

 

 

4.3.9 

* : factory preset 

4.3.1  Control Voltage Selection 

Set the jumper 18 according to the control voltage as shown below: 

 

4.3.2  Total Resistance Setting for Voltage Control 

If a certain resistance is required at voltage control, then solder in a resistor at position 
R6.  

Resistance FDS  200 

Ω  250 Ω  320 Ω  400 Ω  500 Ω  630 Ω 

800 

Ω 

1k 

Ω 

12 VDC [

Ω/W] 

250 /1  330 /½   470 /½  680 /½  1k /¼  1.8k /¼  3.9k /¼ 

24 VDC [

Ω/W] 

220 /4  270 /3 

390 /2 

510 /2  680 /1 

910/1 

1.33k /1  2k /½ 

CN18 

24 VDC * 

CN18 

12 VDC 

* : factory preset 

Summary of Contents for IP-EN1-EB

Page 1: ...IP EN1 EB provides a general fault output with a switch over relay that can be equipped with optional resistors for a surveillance of the connected fire detection system FDS the surveillance must be...

Page 2: ...Breaking a contact Emergency Activation VX making the contact Silencing VX 9 4 3 7 Voltage Emergency Activation VX SX no voltage Emergency Reset VX SX Silencing SX 10 4 3 8 Voltage Emergency Activatio...

Page 3: ...1 Failure reset key lock 2 power indicator 3 emergency mode indicator 4 general fault indicator 5 CPU fault indicator 6 power fault indicator 7 fireman microphone fault indicator 8 fuse rupture indica...

Page 4: ...Jumpers CN6 CN8 for selection of contact or voltage control of FDS 7 Insertion place for resistor R6 for resistance matching to FDS chapter 4 3 2 8 Earth connector when using the emergency control inp...

Page 5: ...When control output is monitored and activation by breaking a contact Insert R1 and R2 as required by surveillance R3 R1 1 3 CN9 R2 R1 2 1 CN9 FDS control voltage CN18 setting CN18 24 VDC CN18 12 VDC...

Page 6: ...SX 2000 system 4 2 1 Make a contact without surveillance Solder in a wire on position R1 Connect to pins 2 and 3 of CN9 to the FDS 4 2 2 Make a contact with surveillance Solder in resistors R1 and R3...

Page 7: ...from the FDS please find the settings in the indicated chapter VX 2000 Emergency activation Emergency reset Silence chapter by contact by voltage make break on off 4 3 3 4 3 4 4 3 5 4 3 6 4 3 7 4 3 8...

Page 8: ...X 2000 Setting Connector Control input Setting CN15 pin 4 any Emergency pattern start CN15 pin 6 any Emergency reset silence emergency pattern stop 4 3 4 Making a Contact Emergency Activation VX break...

Page 9: ...X 2000 Setting Connector Control input Setting CN15 pin 4 any Emergency reset silence emergency pattern stop CN15 pin 6 any Emergency pattern start 4 3 6 Breaking a contact Emergency Activation VX mak...

Page 10: ...2000 Setting Connector Control input Setting CN15 pin 4 any Emergency pattern start CN15 pin 6 any Emergency reset silence emergency pattern stop 4 3 8 Voltage on Emergency Activation VX voltage off S...

Page 11: ...2000 Setting Connector Control input Setting CN15 pin 4 any Emergency reset silence emergency pattern stop CN15 pin 6 any Emergency pattern start 4 3 10 Voltage off Emergency Activation VX Voltage on...

Page 12: ...2 to the CPU OFF output of the VX 2000 connect to pins 2 and 3 5 CN15 provides the access to 4 control inputs of the VX 2000 that are not used by the indication panel and can be used for other control...

Page 13: ...pen circuit ground fault for each loudspeaker line tab Speaker 8 each VX 2000DS connection to VX 2000SF tab Power supply 5 CPU fault CPU OFF control output Only connection no setting 6 Power fault Con...

Page 14: ...Failure Output Select a free line in the failure pattern list make a new failure pattern and select the tab Equipment In the list External Fault CIN make a check at the control input used for receivi...

Page 15: ...f zones The fire areas should be declared by the responsible party e g fire brigade fire expert who is aware of the emergency concept Failures in of up to 8 fire areas can be indicated The control out...

Page 16: ...For details refer to table CN15 connections 7 Connect to control output for programmed general fault pins 1 and 3 CN7 main connections CN15 connections Pin no indication Pin no indication 1 Power LED...

Page 17: ...area 7 3 COM ground 4 COM ground 5 Fault in fire area 5 6 Fault in fire area 6 7 Fault in fire area 8 For the connections to the SX 2000 components connections refer to 6 2 Connections at SX 2000 Com...

Page 18: ...fault indication of the indication panel 6 5 CPU fault 6 Power fault Any control output 1 to CN7 pin 5 select DS LINK select the Failure status output for controlling the power fault indication of th...

Page 19: ...ailures in of up to 8 fire areas can be indicated Any control output can be used for that Setting by the SX 2000 Setting Software 1 In the surveillance settings make a check for each speaker zone that...

Page 20: ...0 mA isolated Dimensions W x H x D 483 x 44 x 47 mm without plugs 19 1U Weight 470 g incl plugs Finish Aluminium brushed black 8 Accessories 2 pin removable screw terminal 2 3 pin removable screw term...

Reviews: