6.3.1.2 Status Indications
No.* Indication of SX-2000 connector
to IP-EN1 connector
Settings
2
Power
-
- (no setting required)
3
Emergency
mode
Any control output
[5]
to CN7 pin 2
Event Setting / System event:
in “Control
output pattern of emergency status
“,
assign the control output [5] for controlling
the indicating of the emergency status
*:
number as on “Appearance Front Panel”, page 3
6.3.2 Indication of Failures in Fire Alarm Areas (option of EN 54-16)
When using this option, then a failure of each fire area must be indicated. Consider that a
fire area may consist of several paging zones, i.e. a fire area can cover a group of zones.
The fire areas should be declared by the responsible party (e.g. fire brigade, fire expert)
who is aware of the emergency concept.
Failures in of up to 8 fire areas can be indicated. Any control output can be used for that.
Setting by the SX-2000 Setting Software
1. In the surveillance settings, make a check for each speaker zone that shall be
monitored.
2. In the pattern settings, control outputs, prepare as many control output pattern as
required for the failure indications of the fire zones.
3. In the pattern settings, failure output, make a failure pattern for each fire area. To do
so, activate the zones in each fire area by a mouse click and select the control output
pattern used for the control of the particular fire zone of the field failure status output
Relation of Control Input connection of the fire area
’s Indication LED
The connectors CN2 and CN7 of the right board (view from rear) contain the control
inputs for the failure indications in the fire areas.
Indication LED FA 1 FA 2 FA 3 FA 4 FA 5 FA 6 FA 7 FA 8 COM COM
Connector no.
CN7 CN7 CN2 CN2 CN7 CN7 CN7 CN7 CN2
CN7
Pin no.
1
2
1
2
5
6
3
7
3
4