IP-EN1-EB Instruction Manual
14
Details to number 9 (network fault):
When using an NX-100S with IES-3000 series Ethernet switch, then the ports used for the
link between decentralised parts of the system on the Ethernet switches must be set for port
surveillance to provide a contact output making a contact when a fault appears. Please refer
to the manual of the IES-3000 Ethernet switch series to do so.
Connect this contact to a control input of the VX-2000. In the activation setting mode of the
VX-2000 setting software, select the functio
n “External Fault CIN” for this control input.
Go to the operation setting mode and select the button [Failure Output]. Select a free line
in the failure pattern list (make a new failure pattern)
and select the tab “Equipment”. In the
list “External Fault CIN”, make a check at the control input used for receiving a fault from
the Ethernet switch. Select control output number 7 for this pattern.
New function Enable Failure Buzzer
The new VX-2000 setting software version 3.1.0 provides a setting for the buzzer control of
the indication panel. When selected, then control output 8 cannot be used for other functions.
5.2.1.2 Status Indications
No.* Indication of
connections
Operation setting mode,
make a check in
2
Power
DC out of
VX-2000DS,
VX-3000DS
- (no setting required)
3
Emergency mode
VX-2000
control output 2
[Emer
gency], tab “Emergency
Output”: Cout-2
*:
number as on “Appearance Front Panel”, page 3
[ ]: button of the main menu of the VX-2000 setting software