10. FAILURE INDICATION
[FV-200RF-AS]
The Error indicator light is red
24V, 230mA
ERROR
MICROPHONE RECEIVER PANEL
FV-200RF-AS
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ON
1 2 3 4
Error Indicator
A communication failure has occurred between the RM-200M and the FV-200RF-AS. The previous status is
automatically restored if communications return to normal.
[RM-200M]
If fault indicator flashes orange, then a communication failure has occurred between the RM-200M and the
FV-200RF-AS.
Communications Failure indicator
If an indicator lights continuously or flashes, the following possible causes may be considered:
Symptom
Possible Cause
Check/Remedy
FV-200RF-AS's
Confirm that the number that has been
Fault indicator
lights red.
set using the setting switch agree with
the actual number of the connected
RM-200M units.
Confirm that the RM-200M's address is set
correctly.
Confirm that there is no fault with the
wiring leading to the RM-200M.
RM-200M's Fault Communication with the FV-200RF-AS Confirm that the number of units that has
indicator flashes
yellow.
is not being performed correctly, or
been set using the FV-200RF-AS's setting
equipment failures may have occurred.
switch agrees with the actual number of
the RM-200M units connected.
Confirm that the unit has the correct
address settings.
Confirm that there is no fault with the
wiring leading to the FV-200RF-AS.
Number of RM-200M setting is
wrongly set in FV-200RF-AS.
Wrong connection between RM-200M
and FV-200RF-AS.